background image

Wilo-Control SC-Fire Electric 

Pioneering for You

2 541 365-Ed.01 / 2014-02-Wilo

de 

  Einbau- und Betriebsanleitung

en 

  Installation and operating instructions

fr 

  Notice de montage et de mise en service

nl 

  Inbouw- en bedieningsvoorschriften 

Summary of Contents for Control SC-Fire Electric

Page 1: ... Fire Electric Pioneering for You 2 541 365 Ed 01 2014 02 Wilo de Einbau und Betriebsanleitung en Installation and operating instructions fr Notice de montage et de mise en service nl Inbouw en bedieningsvoorschriften ...

Page 2: ...Fig 1 SPRINKLER PUMP MOTOR SUPPLY NOT TO BE SWICHED OFF IN THE EVENT OF FIRE I ON 0 OFF 1 2 ...

Page 3: ...3 1 6 7 5 4 ...

Page 4: ...Fig 2 2 3 1 5 4 6 10 9 7 8 ...

Page 5: ......

Page 6: ...easurement board converting current and voltage values Note regarding the main switch Power supply for the sprinkler pump motor DO NOT SWITCH OFF IN THE EVENT OF A FIRE Fig 2 Switchgear display elements 1 LED green Operational standby 2 LED green Pump operation 3 LED yellow False start 4 LED white Sprinkler request 5 LED white Float switch request 6 LED yellow Collective fault 7 LED green and butt...

Page 7: ...formation is disregarded CAUTION There is a risk of damaging the pump unit Cau tion implies that damage to the product is likely if this information is disregarded NOTE Useful information on handling the product It draws attention to possible problems Information that appears directly on the product such as Direction of rotation arrow Identification for connections Rating plate Warning sticker mus...

Page 8: ...ture of spare parts will impair the safety of the product personnel and will make void the manufacturer s declarations regarding safety Modifications to the product are only permissible after consultation with the manufacturer Original spare parts and accessories authorised by the manufacturer ensure safety The use of other parts will absolve us of liability for consequential events 2 8 Improper u...

Page 9: ...ol an individual electric pump in sprinkler systems in accordance with EN 12845 The pump can be switched on and off by the control depending on the pressure The system s operating statuses such as standby pump operation fault etc are displayed visually by LEDs on the door and operating parameters such as current or voltage values are shown on the display The system is operated using the rotary kno...

Page 10: ...llective fault signal Fig 2 item 6 lights up yellow If a fault occurs the pump nevertheless starts or continues running Once the voltage is back within the tolerance range the fault is self acknowledging The signal lamp Fig 2 item 6 goes out and the signal lamp Fig 2 item 1 lights up green again Current monitoring The pump current is monitored while the pump is in operation To do this the correct ...

Page 11: ...enu level press it in order to select and confirm Information appears on the display as shown in the sample illustration below 4 4 1 2 3 5 Item Description 1 Menu number 2 Value display 3 Units display 4 Standard symbols 5 Graphic symbols The following graphic symbols are used Symbol Function description Availability Go back brief press one menu level long press main screen all EASY menu all EXPER...

Page 12: ...ting mode application all Stand by all Operating data all Switchgear data Controller type ID number software firmware all Operating hours all Pump s operating hours all Switchgear s switching cycles all Pump s switching cycles all Communication all Output parameters all SSM parameter all Set motor speed Diesel Symbol Function description Availability ...

Page 13: ...inkler pressure switch all Pump priming tank float switch all Heating Diesel Engine oil Diesel Motor temperature thermostat Diesel Cooling water temperature Diesel Belt break Diesel False start Electrical equipment Pressure Electrical equipment Mains power supply Electrical equipment Voltmeter all Ampere meter all Star delta switching Electrical equipment Symbol Function description Availability ...

Page 14: ...l Duration all Power meter Electrical equipment Communication parameters all Modbus all BACnet all Factory setting all Resetting the settings to the factory settings all Alarm counter all Maintenance interval all Reset all Motor speed Diesel Set motor speed Diesel Minimum speed for motor in operation Diesel Reset starting counter Diesel Symbol Function description Availability ...

Page 15: ...nglish Installation and operating instructions Wilo SC Fire Electric 35 Navigation in the individual menus as well as the parameter input are described in the following example selecting the transformer ...

Page 16: ...n the motor is running the present pump cur rent in all three live wires is shown alternately on the display The EASY menu allows you to make settings for the supply voltage rated pump current and the pump s performance The EXPERT menu contains other settings that can be used for a detailed setting of the switch gear The parameter menu for all settings that influence operation The setting menu for...

Page 17: ...ng operations periods Setting the duration for monitoring of the pump s electric output electric false start 0 70 120 Setting the duration for monitoring of the pump s hydraulic output hydraulic false start 0 70 120 The setting menu for the delays Start delay when pressure switch trips 1 10 Start delay when float switch trips 1 10 Menu no Display Description Parameter range Factory setting ...

Page 18: ...Delay in event of error message from current monitoring 0 1 20 Star delta changeover time 0 5 60 Buffer time between deactivation of star contac tor and activation of delta contactor 0 00 0 05 1 0 Communication Display of currently activated fieldbus OFF Modbus BAC net GSM Pump menu Menu no Display Description Parameter range Factory setting ...

Page 19: ...tric 39 Drives on off OFF ON Information Current operating values Voltage values Voltage between conductors L1 and L2 Voltage between conductors L1 and L3 Voltage between conductors L2 and L3 Current values Menu no Display Description Parameter range Factory setting ...

Page 20: ... 01 2014 English Pump current in L1 Pump current in L2 Pump current in L3 Output values Pump output L1 Pump output L2 Pump output L3 Status information Menu no Display Description Parameter range Factory setting ...

Page 21: ...ctric 41 System status or readiness Status of pressure switch Status of float switch Operating data Total running time of the system Total running time of pump Unit switching cycles Pump s switching cycles Menu no Display Description Parameter range Factory setting ...

Page 22: ...2014 English System data System type Serial number as ticker format Software version Firmware version Settings Sensor settings Transformer selection 30 1000 Menu no Display Description Parameter range Factory setting ...

Page 23: ...rance limit for supply voltage 0 10 Upper tolerance limit for supply voltage 0 10 Lower tolerance limit for rated pump current 0 10 Upper tolerance limit for rated pump current 0 10 Setting for minimum output necessary for detec tion that pump has started 0 80 100 Signal output parameters Menu no Display Description Parameter range Factory setting ...

Page 24: ...lt signal Acknowledgement process for fault signal Not store ON store Logic reversal of input signal Fall Rise Activation of configurable fault signal OFF ON Fault active Always Only when pump in operation Ever Pump Response delay 0 60 Fault signals Menu no Display Description Parameter range Factory setting ...

Page 25: ...n Acknowledgement Fig 2 item 10 Pressing the button resets all the error messages or signal lamps provided that the cause of the error no longer exists 6 2 3 Switchgear display elements Operational standby The signal lamp Fig 2 item 1 lights up green if the power supply is connected activated via the main switch and the power supply is within the configurable tolerance range see menu 5 4 1 0 and 5...

Page 26: ... injury Improper electrical connections can lead to fatal electric shocks Have the electrical connection established by an electrician approved by the local electricity sup plier only and in accordance with local regula tions Observe the installation and operating instruc tions for the pumps and accessories Disconnect the power supply before any work Warning Danger of electric shock There is a pot...

Page 27: ...130 6 4 0 0 094 12 4 0 0 077 18 5 5 0 115 6 5 5 0 083 12 5 5 0 069 18 7 5 0 059 6 7 5 0 042 12 9 0 11 0 0 037 6 9 0 11 0 0 027 12 15 0 0 024 6 15 0 0 017 12 3 400 V 2 pole S D starting 5 5 0 252 18 5 5 0 220 24 5 5 0 198 30 7 5 0 217 6 7 5 0 157 12 7 5 0 130 18 7 5 0 113 24 9 0 11 0 0 136 6 9 0 11 0 0 098 12 9 0 11 0 0 081 18 9 0 11 0 0 071 24 English Installation and operating instructions Wilo S...

Page 28: ...ing to the pump s rated current is to be inferred from the pump s rating plate Menu 1 2 1 3 Display of the pump s capacity The value used for thecapacityresultsfromthesetvaluesforvoltage and current under menu 1 2 1 1 and menu 1 2 1 2 Menu 5 2 1 0 Setting of the transformer type primary current measuring range Information relating to the transformer type can be found on the trans former s rating p...

Page 29: ...s configured for 16 faults The fault memory can be called up using menus 6 1 0 1 6 1 1 6 Code Fault description Causes Remedy E54 0 No bus communication to HMI board Connection to HMI board inter rupted Check connection Request customer service E4 0 Undervoltage Supply voltage too low on mains side Check mains voltage mains supply check fuses E5 0 Overvoltage Supply voltage too high on mains side ...

Page 30: ......

Page 31: ......

Page 32: ...Pioneering for You WILO SE Nortkirchenstraße 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com ...

Reviews: