en
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
51
Main menu
1
5
3
2
Fig. 75:
Acknowledge fault
✓
All faults rectified.
1.
Press the operating button for 3 s.
⇒
Menu 1.00 appears.
2.
Turn the operating button until menu 6 appears.
3.
Press the operating button.
⇒
Menu 6.01 appears.
4.
Press the operating button.
5.
Change the value to “reset”: Turn the operating button.
6.
Press the operating button.
▶
The fault indication is reset.
Easy Actions menu
✓
All faults rectified.
1.
Starting the Easy Actions menu: Turn the operating button 180°.
2.
Select menu item “Err reset”.
3.
Press the operating button.
▶
The fault indication is reset.
Fault acknowledgement failed
If there are further faults, the faults are displayed as follows:
•
The fault LED lights up.
•
The error code of the last fault is shown in the display.
All other faults can be called up from the fault memory.
If all faults have been rectified, acknowledge the faults again.
11.4
Fault memory
The switchgear stores the last ten faults in the fault memory. The fault memory works ac-
cording to the first in/first out principle. The faults are displayed in descending order in the
menu items 6.02 to 6.11:
•
6.02: the last/latest fault
•
6.11: the oldest fault
11.5
Error codes
The functions may operate differently depending on the software version. That is why a
software version is included with every error code.
The details regarding the software version used can be read on the rating plate or displayed
via menu 4.24.
Code*
Fault
Software
version
Cause
Remedies
E006
Rotating field error
all
•
Incorrect rotating field
•
Operation via single-phase current
connection
•
Establish a clockwise rotating field at the
mains connection.
•
Deactivate rotating field monitoring
(menu 5.68)!
E014.x
Leakage detection
all
The moisture probe of the connected
pump was tripped.
See the installation and operating instruc-
tions of the connected pump
E040
Fault, level sensor
all
No connection to the sensor
Check the connection cable and sensor. Re-
place the defective component.
E062
Dry-running protection
active** / min. water
level active**
all
•
Operating mode
“drain”
:
Dry-running level reached
•
Operating mode
“fill”
:
Min. water level, below minimum
value
•
Check inlet and system parameters.
•
Check that the float switch is working
correctly, replace the defective compo-
nent.
E066
High water alarm active
all
High water level reached
•
Check inlet and system parameters.
•
Check that the float switch is working
correctly, replace the defective compo-
nent.