Installation and operating instructions Wilo-Control EC-Fire
41
4 Application (intended use)
The EC-Fire switchgear is used for the pressure-
dependent and volume-flow dependent control
of up to 3 constant speed pumps in fire extin-
guishing systems. Signal detection occurs by
means of pressure switch, pressure sensor, flow
switch or volume flow sensor.
Intended use also means compliance with this
manual. Any other use is regarded as
non-compliant with the intended use.
5 Product information
5.1 Type key
5.2 Technical data
5.2.2 Inputs
• 1x analogue input 4 – 20 mA for the
pressure sensor
• 1x analogue input 4 – 20 mA for the volume
flow sensor
• 1x digital input for the pressure switch
• 1x digital input for the flow switch
• 1x digital input for the protection against low
water level
• 1x digital input for remote switch-off of all
pumps (Ext. Off)
5.2.3 Outputs
• 1x potential-free changeover contact for SSM
• 1x potential-free changeover contact for SBM
• 1x potential-free normally closed contact for ESM
per pump
• 1x potential-free normally open contact for EBM
per pump
• 1x output 24 V DC (max. 4 VA) for connection of a
signal lamp etc.
• 1x analogue output 0 – 10 V for display of the
actual pressure value
5.3 Scope of delivery
• Switchgear
• Installation and operating instructions
• Circuit diagram (for devices in a metal
housing only)
5.4 Accessories and options
5.4.1 Accessories
• Float switch for dry-running protection
• Pressure switch for dry-running protection
• Pressure switch for pump control
• Pressure sensor for pump control
• Volume flow sensor for pump control
• Rotating beacon 24 V DC
NOTICE
In the event that the EC-Fire switchgear is
delivered in a Wilo system, the accessories may
already be fitted.
Example:
W-CTRL-EC-F-2x12A-T34-DOL-CPI-WM
W
W = WILO
CTRL
Switchgear
EC
EC = Easy Control switchgear for
fixed-speed pumps
F
Control for fire-extinguishing system
2x
Max. number of pumps that can be
connected
12A
Max. rated current in ampere per pump
T34
Mains connection:
T = three-phase current (3~)
34 = live wire, e.g. 380 – 400 V
DOL
Direct activation of the pump(s)
CPI
Insulation monitoring device(s) installed
for pumps in the switchgear
WM
Wall fixation
5.2.1 Switchgear
Mains connection:
See rating plate
Max. current consumption:
See rating plate
Activation type:
Direct
Ambient/operating temperature:
0…+40 °C
Storage temperature:
-30…+60 °C
Max. relative humidity:
90 %, non-condensing
Protection class:
IP54
Control voltage:
See rating plate
Housing material:
Depending on version:
Polycarbonate, UV-resistant
Steel sheeting, powder coated
Electrical safety:
Pollution degree II
Summary of Contents for Control EC-Fire
Page 7: ...Fig 9 Fig 10 Fig 11...
Page 8: ...Fig 12 Fig 13 Fig 14...
Page 9: ...Fig 15 Fig 16...
Page 10: ......
Page 13: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 3...
Page 16: ...Deutsch 6 WILO SE 06 2018...
Page 43: ...Deutsch Einbau und Betriebsanleitung Wilo Control EC Fire 33...
Page 45: ...English Installation and operating instructions Wilo Control EC Fire 35...
Page 48: ...English 38 WILO SE 06 2018...
Page 75: ...English Installation and operating instructions Wilo Control EC Fire 65...
Page 77: ...Fran ais Notice de montage et de mise en service Wilo Control EC Fire 67...
Page 80: ...Fran ais 70 WILO SE 06 2018...
Page 109: ......
Page 110: ......