6. Faults
CAUTION!
Physical injuries, damage to property
If faults cannot be eliminated by means of the listed measures, the wire
rope force transducer must be decommissioned immediately.
▶
Contact the manufacturer.
▶
If a return is needed, please follow the instructions given in chapter 9.2
“Return”.
For contact details see chapter 1 “General information” or the back page
of the operating instructions.
Faults
Causes
Measures
No output signal
No or wrong supply voltage,
surge current
Rectify the supply voltage
Cable break
Check the continuity
No or wrong output signal
Wrong pin assignment
Check pin assignment
Readjustment after installation
not carried out
Carry out readjustment after
installation
Deviating zero-point signal
Overload, load offset, wrong
connection
Consult the manufacturer
Readjustment after installation
not carried out
Carry out readjustment after
installation
Constant output signal
when changing force
Mechanical overload,
wrong pin assignment
Consult the manufacturer
Mounting on the rope is not
correct
Check and adjust mounting to
the rope
5. Commissioning, operation / 6. Faults
Cable assignment
Cable
colour
2-wire
Red
UB+/S+
Black
0V/S-
5.5.1 Pin assignment, analogue output, model F9204