21
WIKA operating instructions, reference pressure sensor, model CPT62I0
EN
14225194.01 12/2018 EN/DE/FR/ES
9.2 Safety-related characteristic values
Power supply circuit CPT62I0
Max. input voltage
U
i
= DC 10.4 V
Max. input current
I
i
= 100 mA
Max. input power
P
i
= 500 mW
Max. internal capacitance
C
i
= 600 nF
Max. internal inductance
L
i
negligible
9.3 Ex approvals
Logo
Description
Country
EU declaration of conformity for CPT62I0
■
EMC directive
■
EN 61326 emission (group 1, class B) and immunity (portable
equipment)
■
Pressure equipment directive
■
PS > 200 bar; module A, pressure accessory
■
RoHS directive
■
ATEX directive
Hazardous areas
Ex i Zone 1 gas
II 2G Ex ib IIC T4
II 2G Ex ib IIC T4 Gb
Ta = -20 ... +50 °C
European Union
EAC
■
EMC directive
■
Pressure equipment directive
■
Hazardous areas (see approval)
Eurasian
Economic
Community
9.4 Certificates
Certificate
Calibration
Standard: 3.1 calibration certificate per DIN EN 10204
Option: DKD/DAkkS calibration certificate
Recommended
recalibration interval
1 year (dependent on conditions of use)
Approvals and certificates, see website
For further specifications see WIKA data sheet CT 11.02 and the order documentation.
9. Specifications