Diagnostics and troubleshooting
79278347
Information on the diagnosis of the samosPRO system can be found in the software manual, Section
"List of all error messages".
Table 35: Troubleshooting on the SP-COP2-ENI module
Error
Possible cause
Possible remedy
Key: LED off /
LED flashes / LED lights up
The SP-COP2-ENI module
does not provide any data.
• The SP-COP2-ENI has been
configured for data trans-
mission to the PLC, but no
Ethernet communication
has been established or the
communication is faulty.
• Duplicate IP address detec-
ted. Another network de-
vice has the same IP
address.
• Incorrectly formatted PRO-
FINET device name
• PROFINET IO must be activated
in the project file. At least one
Ethernet link must be establis-
hed. Check the Ethernet wiring,
check the Ethernet settings in
the PLC and in samosPLAN
6.
• Correct the IP address and
switch the system off and on
again.
• Compare the device name
between the PROFINET master
and the SP-COP2-ENI module.
LED PWR/EC
Green
LED LINK
Green
LED /ACT
Yellow
MS LED
Green
The SP-COP2-ENI module
does not provide any data.
• Configuration required.
• The configuration has not
yet been fully transmitted.
• The module version does
not support any PROFINET
IO.
• Configure the SP-COP2-ENI
module with a project file in
which PROFINET IO is activated
and transfer the configuration
to SP-COP2-ENI module.
• Use an SP-COP2-ENI device
starting with module version B-
xx.
LED PWR/EC
Green
LED LINK
Green
LED /ACT
Yellow
MS LED
/
Red/gr
een
The SP-COP2-ENI module
does not provide any data.
• The samosPRO system is in
the stop state.
• Start the controller module
(switch to Run mode).
LED PWR
Green
LED LINK
Green
LED /ACT
Yellow
MS LED
Green (1 Hz)
The SP-COP2-ENI module
does not provide any data.
• The IP address for the SP-
COP2-ENI module is assig-
ned by a DHCP server.
Following a restart of the
SP-COP2-ENI module or the
DHCP server, another
address was allocated to
the SP-COP2-ENI module,
which is unknown to the
PLC.
• Either assign the SP-COP2-ENI
module a permanent IP
address or reserve a perma-
nent IP address for the SP-
COP2-ENI module in the DHCP
server (manual assignment u-
sing the MAC address of the SP-
COP2-ENI module).
LED PWR/EC
Green
LED LINK
Green
LED /ACT
Yellow
MS LED
Green
The SP-COP2-ENI / the
samosPRO system is in the
• The SP-COP2-ENI module is
not properly connected to
• Insert the I/O module correctly.
Clean the connection plug and