SP-SDI input/output expansion module
888397323
Description
888398859
The SP-SDI module is an input expansion with eight safe inputs. If fulfills the following tasks:
• Monitoring of connected sensors
Connecting devices [ch. 4, p. 43]
• Forwarding of input information to the controller module
The SP-SDI module cannot be operated alone and always requires an SP-COP controller modu-
le (see "samosPLAN
6" programming software).
It is possible to use multiple SP-SDI modules simultaneously (see
). The voltage of the internal logic and the test outputs is supplied via the program remo-
vable storage device and the internal safety bus.
ATTENTION
Limited short-circuit detection in the input circuits
• One SP-SDI has two test signal generators. One test signal generator is responsible for
the odd-numbered test outputs (X1, X3, X5, and X7), while the other is responsible for
the even-numbered test outputs (X2, X4, X6, and X8).
• Short-circuits between test signal generators of a SP-SDI or SP-SDIO module are detec-
ted. Between different modules the short circuit detection is then only ensured if the test
gaps of the test signal generators are < 4 ms and the test periods
≥
200 ms. Short-circuits
past 24 V DC (after High) at inputs that are connected to test outputs are detected inde-
pendently of the length of the test gaps.
• Please ensure that the odd-numbered test outputs (X1, X3, X5, and X7) at the SP-SDI are
connected to a common test signal generator and that the even-numbered test outputs
(X2, X4, X6, and X8) are connected to another common test signal generator. Therefore,
short-circuits between the odd-numbered test outputs (X1, X3, X5, and X7) cannot be de-
tected. The same applies accordingly to the even-numbered test outputs X2, X4, X6, and
X8.
Make note of this during wiring (e.g. through separate routing or protected lines)!
3.9
3.9.1
Summary of Contents for samos PRO COMPACT
Page 1: ...samos PRO samos PRO COMPACT Hardware Manual Doc no BA000966 Last Update 08 2017 8151...
Page 103: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 103 Declaration of Conformity Page 2...
Page 104: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 104 Declaration of Conformity Page 3...
Page 105: ...Appendix Wieland Electric GmbH BA000966 08 2017 8151 105 Declaration of Conformity Page 4...