Wieland podis?MOT FA C 1I3O Operating Instructions Manual Download Page 48

9.

Wieland Electric  |  BA000341  |  02.2007    

Malfunctions

  |  9

9.

 

Replacing the hood

The electronics module is built into the hood (electronics cover). If the electronics module is 
defective, the hood must be replaced.

WARNING

•  All electrical installations and connections may be performed only by trained electricians. 
•  The applicable safety and accident prevention regulations must be observed.
•  Before opening and removing the electronics cover, the entire flat cable must be de-ener-

gized.

Proceed as follows to replace the hood:

1. Remove the four fastening screws of the hood.
2. Unplug connector X6 (and X7 for 83.219.xx01.2).
3. Replace the hood with a new one. 
4. Plug connector X6 (and X7 for 83.219.xx01.2) into the connection in the hood.
5. Attach the hood with the four fastening screws. 
•  Ensure that the unit is tight and that no connecting cables have been pinched.
•  The hood has been replaced.
6. Finally, check the AS-i addressing.

Hood with integrated 
electronics

Pluggable connection 
between hood and base

Base with connection technology
(hidden by cover plate)

podis®MOT (opened)

Summary of Contents for podis?MOT FA C 1I3O

Page 1: ...podis MOT FA C CM CP 3I 1I4O podis MOT FA C 2I1O 1I3O podis MOT FA I C 1I4O Decentral Field Distributor at AS Interface Operating Instructions Doc No BA000341 Revision A 2007 Wieland Electric GmbH...

Page 2: ......

Page 3: ...information and help required for proper operation of your podis system If you still have questions or require any help our experts are gladly at your disposal using the contact options listed below...

Page 4: ...cuments are provided by suppliers Operating manual of the AS i master Operating instructions of the drives All trademarks listed in this documentation and any trademarks copyrighted by third parties a...

Page 5: ...ay elements 2 2 Connections at the podis MOT FA C 3I 1I4O 2 2 Connections at the podis MOT FA CM 3I 1I4O 2 3 Connections at the podis MOT FA CP 3I 1I4O 2 3 Connection assignment of AS i socket 2 4 Con...

Page 6: ...onnection to the AS interface 6 4 6 3 Connection of sensors and actuators 6 5 Table of connection variants 6 5 6 4 Drive connection 6 5 Core assignment of connecting line 6 5 Connector assignment of r...

Page 7: ...h enables them to perform operations on equipment of automation technology and who is authorized to commission ground and identify electrical circuits and devices or systems according to the standards...

Page 8: ...lying supply voltage to the field distributor the top part electronics cover must be installed and fastened onto the bottom part Before removing the top part electronics cover the energy bus segment m...

Page 9: ...cturer and user must must therefore observe the safety regulations of machine direc tive 89 392 EWG For the specific application case the national accident prevention regulations apply such as VBG 4 0...

Page 10: ...1 8 Prevention of property damages and bodily injuries The voltage values must not be less than or greater than the voltage values listed in the techni cal data since it may lead to malfunctions or d...

Page 11: ...decentral field device Using prefabricated M12 connecting lines allows for connecting 2 wire and 3 wire sensors to the three free inputs The sensors are supplied in the podis field distributor from t...

Page 12: ...d base is implemented via a cable harness from the base connected to a PCB pluggable connector in the hood 2 4 Connections control and display elements 6 1 5 2 4 3 Connections at the podis MOT C 3I 1I...

Page 13: ...ital M12 input to connect a sensor 6 X1 Interface to the drive R Repair switch The podis MOT 83 210 xxy1 4 also features a repair switch R 6 1 5 2 4 3 Connections at the podis MOT FA CP 3I 1I4O 1 ADDR...

Page 14: ...escription Note 1 24 V 24 V sensor supply 2 IN Digital inputs 3 0 V 0 V of sensor supply 4 IN Pin 4 connected with pin 2 5 Ground Equipotential bonding The digital inputs at X3 X4 and X5 are supplied...

Page 15: ...ection The supply is provided by an external 24 V power supply No Color Designation Meaning I O bit 1 green AS i power AS i power ok 2 red AS i fault Fault of AS i 3 yellow IN 0 Input M12 E0 4 yellow...

Page 16: ...Wieland Electric BA000341 02 2007 podis MOT FA C CM CP 3I 1I4O Device Description 2 2 5 Technical information Installation dimensions 83 210 xx01 2 Installation dimensions 83 210 xxy1 4...

Page 17: ...Wieland Electric BA000341 02 2007 2 podis MOT FA C CM CP 3I 1I4O Device Description Installation dimensions 83 210 0005 2...

Page 18: ...4 10 6 7 8 9 PE L1 L2 L3 PE M ok M op M fwd M rev M f1 f2 24V IN1 0V IN1 ASI ASI X6 ADDR 1 2 3 xx 1 2 3 5 PE 4 6 24V IN0 0V IN0 24V IN2 0V IN2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 IN3 OUT0 OUT1 OUT2 OUT3 5...

Page 19: ...7 8 9 PE L1 L2 L3 PE M ok M op M fwd M rev M f1 f2 24V IN1 0V IN1 ASI ASI X6 ADDR 1 2 3 xx 1 2 3 5 PE 4 6 24V IN0 0V IN0 24V IN2 0V IN2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 IN3 OUT0 OUT1 OUT2 OUT3 5 6 1 2 3...

Page 20: ...7 8 9 L1 L2 L3 PE M ok M op M fwd M rev M f1 f2 24V IN1 0V IN1 ASI ASI X6 ADDR 1 2 3 xx 1 2 3 5 PE 4 6 24V IN0 0V IN0 24V IN2 0V IN2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 IN3 OUT0 OUT1 OUT2 OUT3 5 6 1 2 3 5 4...

Page 21: ...odis field distributor from the AS interface The output via M12 is an electronic output with a maximum load of 24 VDC and 0 5 A This A0 output is available at M12 as well as PIN 6 of the connector int...

Page 22: ...between hood and base is implemented via a cable harness from the base connected to a PCB pluggable connector in the hood 3 3 Connections control and display elements 6 1 5 2 4 3 Connections at the p...

Page 23: ...ound Equipotential bonding The digital inputs at X4 and X5 are supplied from AS i internal Digital outputs X3 view from outside onto socket contacts Pin Brief description Note 1 NC NC 2 NC NC 3 0V 0V...

Page 24: ...Wieland Electric BA000341 02 2007 podis MOT FA C 2I1O 1I3O Device Description 3 3 4 Technical information Installation dimensions 83 212 xx01 2...

Page 25: ...IN0 PE 10 1 2 3 5 4 10 6 7 8 9 PE L1 L2 L3 PE M ok OUT0 M Run OUT2 OUT3 24V IN1 0V IN1 ASI ASI ADDR 1 2 3 xx 1 2 3 5 PE 4 6 n c n c OUT0 24V IN2 0V IN2 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 IN3 OUT0 OUT1 OUT...

Page 26: ...Wieland Electric BA000341 02 2007 podis MOT FA C 2I1O 1I3O Device Description 3...

Page 27: ...ween field distributor and drive is implemented using a prefabricated connecting line The field distributor is directly connected to the AS i hand held terminal 83 209 2204 0 and addressed using the A...

Page 28: ...base connected to a PCB pluggable connector in the hood 4 3 Connections control and display elements 2 1 Connections at the podis MOT 1 ADDR Connection of the AS i hand held terminal 2 X1 Interface to...

Page 29: ...ower ok 2 red AS i fault Fault of AS i 6 yellow M ok Motor is operational E3 7 yellow M op Motor electronics on A0 8 yellow M fwd CW rotation of motor A1 9 yellow M rev CCW rotation of motor A2 The st...

Page 30: ...Wieland Electric BA000341 02 2007 podis MOT FA I C 1I4O Device Description 4 4 4 Technical information Installation dimensions 83 219 xx01 2...

Page 31: ...1 L2 L3 PE X0 X1 N AS i LED s PE 10 5 6 7 8 9 1 2 3 5 4 10 6 7 8 9 PE L1 L2 L3 PE M ok M op M fwd M rev X6 ADDR 1 2 3 xx 1 2 3 5 PE 4 6 IN3 OUT0 OUT1 OUT2 OUT3 1 2 3 5 4 10 6 7 8 9 4 X7 AS i AS i AS i...

Page 32: ...Wieland Electric BA000341 02 2007 podis MOT FA I C 1I4O Device Description 4...

Page 33: ...three M4 screws not supplied To install the unit on the substructure proceed as follows 1 Copy the borehole diagram see the corresponding figure for the installation dimensions onto the substructure T...

Page 34: ...Wieland Electric BA000341 02 2007 Mechanical Installation Assembly 5...

Page 35: ...circuits together with low voltage circuits using one line the line must be protected against mechanical damage in areas of risk e g cable channel steel pipe or similar protection 6 1 Connection to th...

Page 36: ...top Use a pneumatic or electrical screwdriver Use Phillips no 1 screwdriver blades with a shaft length of at least 45 mm Maximum torque 1 Nm Screwed in penetrating screws must not be unscrewed again W...

Page 37: ...nd X7 for 83 219 xx01 2 between hood and base see section 2 2 Mechanical design housing and separate the hood from the base 3 Remove the two fastening screws open up the base and place the flat cable...

Page 38: ...no connecting cables have been pinched The podis field distributor is connected to the energy bus 6 2 Connection to the AS interface Connect the AS i interface of the podis field distributors 83 210...

Page 39: ...Digital outputs M12 Digital outputs to consumer 83 210 0005 2 3 1 4 83 210 xx01 2 4 3 1 4 83 212 xx01 2 2 1 1 3 83 219 xx01 2 1 4 WARNING Unused connections must be fitted with M12 caps to ensure enc...

Page 40: ...wer supply If the variant with industrial connector and revosBASIC is selected please observe the order ing information from the drive manufacturer Pin Designation Meaning 1 L1 Motor lead voltage U 2...

Page 41: ...tributor 3 Preset the address See the operating instructions of the addressing device 4 Remove the addressing cable and close the addressing socket again with the cap NOTICE Some addressing devices ca...

Page 42: ...Wieland Electric BA000341 02 2007 Commissioning 7...

Page 43: ...ort circuit of AS i voltage off AS i communication is correct yellow IN 0 constantly on Signal voltage IN0 high level off Signal voltage IN0 low level yellow IN 1 constantly on Signal voltage IN1 high...

Page 44: ...low level yellow IN 1 constantly on Signal voltage IN1 high level off Signal voltage IN1 low level yellow IN 2 constantly on Signal voltage IN21 high level off Signal voltage IN2 low level yellow M ok...

Page 45: ...cipate in normal data traffic e g slave address 0 flashing Periphery error e g short circuit of AS i voltage off AS i communication is correct yellow M ok constantly on Drive operational off Drive not...

Page 46: ...Wieland Electric BA000341 02 2007 Operation 8...

Page 47: ...below is not sufficient to remove the malfunction contact the technical support of Wieland Status LED malfunction Cause Remedy AS i fault flashes constantly AS interface communication error slave does...

Page 48: ...the entire flat cable must be de ener gized Proceed as follows to replace the hood 1 Remove the four fastening screws of the hood 2 Unplug connector X6 and X7 for 83 219 xx01 2 3 Replace the hood wit...

Page 49: ...nputs supply via AS i 3 IN0 IN1 IN2 via M 12 Digital inputs via 24V_EXT 1 IN3 Input current typ 5 mA Signal level Vhigh Vlow 15 V 31 5 V 3 V 5 V Signal delay typ 1 ms Digital outputs Digital outputs t...

Page 50: ...nputs via 24V_EXT 1 IN3 Input current typ 5 mA Signal level Vhigh Vlow 15 V 31 5 V 3 V 5 V Signal delay typ 1 ms Digital outputs Digital outputs to motor via 24V_EXT 4 of which OUT0 also via M 12 X3 O...

Page 51: ...al inputs Digital inputs via AS i 1 M ok Input current typ 5 mA Signal level Vhigh Vlow 15 V 31 5 V 3 V 5 V Signal delay typ 1ms Digital outputs Outputs to the motor supply via AS i 4 Output voltage a...

Page 52: ...Cable type 0 Standard 1 Reserved f r special solutions Cable length 00 no cable 05 500mm 10 1000mm 15 1500mm 20 2000mm 25 2500mm 30 3000mm Type designation Main catalog number 10 0 1 2 1 revosBASIC 1...

Page 53: ...10 1001 2 but line length 2 5m 83 210 2501 2 same as 83 210 1001 2 but line length 3 0m 83 210 3001 2 podis MOT FA CM 3I 1I4O same as 83 210 1001 2 but with repair switch and line length 1m 83 210 100...

Page 54: ...10 9G1 5 gray cable cross section 1 5mm length 1 0m 83 312 1002 1 same as 83 312 1002 1 but line length 1 5m 83 312 1502 1 same as 83 312 1002 1 but line length 2 0m 83 312 2002 1 same as 83 312 1002...

Page 55: ...1O 1I3O podis field distributors for decentral consumers drives on the podis flat cable energy bus in IP65 with integrated AS i slave 4I 4O AS interface yellow cable connection external via M12 Two di...

Page 56: ...dustrial connector revosBASIC as interface to consumer drive 83 219 1001 2 same as 83 219 1001 2 but line length 1 5 m 83 219 1501 2 same as 83 219 1001 2 but line length 2 0 m 83 219 2001 2 same as 8...

Page 57: ...10 Wieland Electric BA000341 02 2007...

Page 58: ......

Page 59: ......

Page 60: ......

Reviews: