The electrical connection on the energy bus flat cable is carried out by screwing in the pen-
etrating screws.
It is recommended to use a cordless driver with adjustable torque.
CAUTION
The following notices must be observed when handling penetrating screws:
• All penetrating screws must be screwed in to the stop.
• Use a pneumatic or electrical screwdriver.
• Use Phillips no.1 screwdriver blades with a shaft length of at least 45 mm.
• Maximum torque 1 Nm.
• Screwed in penetrating screws must not be unscrewed again. When removing a podis
field distributor from the flat cable, use the podis sealing sleeve (Z1.005.6553.1) to seal
the contact positions.
• Only original screws from Wieland Electric may be used.
• Operation with torn off screws is not allowed.
• Cable ties must not be removed, and the cover of the penetrating screws (connecting
plate) must be inserted after complete installation.