Installation instructions (translation from original)
gesis®
GST18®
GST18® connector 3…6-pole, screw connection
Wieland Electric GmbH
Brennerstraße 10 – 14
96052 Bamberg
Phone +49 951 9324-0
Fax
+49 951 9324-198
Doc. #
BA000180
– 12/2019 (Rev. C)
gesis®
GST18®
EN
NOTE
•
All
gesis®
components may only be installed, commissioned and serviced by qualified
•
electricians.
•
Persons who install, operate or maintain this device must have read and understood
these instructions.
•
The relevant standards, guidelines, regulations and provisions of the respective country
must be observed.
•
Protective measures and mechanisms must correspond to applicable regulations.
•
Damaged products may neither be installed nor operated.
•
In case of a defect, please return the component to Wieland Electric.
•
Never use components from third-party manufacturers. No guarantee shall be offered
for damage resulting from a combination with third-party components.
•
Please keep these instructions in a safe place for later reference.
CAUTION
•
No hazardous interchangeability with systems based on IEC 60309, IEC 60320, IEC 60906
and with national male and socket systems for home use.
•
Interchangeability between installation connector systems from different manufacturers
is not automatically prevented by compliance with EN 61535.
•
Compatibility with products from other manufacturers cannot be guaranteed.
•
Installation connectors do not replace national household connector system.
•
In easily accessible areas, unused connectors must be fitted with closing pieces and the
test openings must be closed off with the molded cover.
1
Strain relief area and connector cross sections
GST18i3
Standard strain relief
(92.93x.3/4x53.x): SR area
6.5 – 10.5 mm
GST18i3
High strain relief
(92.93x.5/6x53.x): SR area
10.5 – 14.5 mm
GST18i4
Standard strain relief
(92.94x.3x53.x): SR area
6.8 – 11.5 mm
GST18i5
Standard strain relief
(92.95x.4x53.x): SR area
7.0 – 13.5 mm
GST18i5
High strain relief
(92.95x.5x53.x): SR area
11.5 – 15.5 mm
GST18i6
Standard strain relief
(92.96x.0358.1): SR area
11.5 – 15.5 mm
GST18i6
High strain relief
(92.96x.0158.1): SR area
10.0 – 12.0 mm
In general:
•
One connection per pole.
•
Connector cross-section for standard strain relief 0.75 … 2.5 mm².
•
Connector cross-section for high strain relief 0.75 … 4 mm².
•
Fine stranded wires can be used without ferrules.
•
Fine stranded wires 4 mm² cannot be used with ferrules.
2
Sheath stripping and insulation removal lengths
All of the following information is given in mm.
2.1
GST18i3
Standard strain relief
High strain relief
2.2
GST18i4 – Standard strain relief
2.3
GST18i5
Standard strain relief
High strain relief
2.4
GST18i6
Standard strain relief
High strain relief
3
Installation with GST18i3 as example
Proceed in the same way for 4…6-pole connectors.
Mind the correct pole assignment.
For built-in and Snap-in device connectors with screw termination, use the same tightening
torque.
4
Removal
Contacting
1
Torque:
0.5 – 0.7 Nm
2
3
4
5
Done!
Torque:
0.5 – 0.7 Nm
Installation of
the strain relief
1
2
black
black
green/yellow
green/yellow
green/yellow
green/yellow