5
Battery lifetime elapsed
Active when the actual calculated battery lifetime exceeds the threshold specified in "Battery lifetime"
field (see no. 15 in section 6.2).
LCD name
Modbus address
Bat. lifetime elapsed
0x4014
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Max. calculated value
6
Battery charge failure
Active when the UPS module could not charge the battery correctly. When active, the battery charger
is disabled. Disconnect the battery to reset the alarm.
LCD name
Modbus address
Bat. charge fail
0x4015
Value 1
Value 2
Inactive (0), Active (1)
Not used
7
Battery SoC <25%
Active when the battery State of Charge is under 25% of the nominal full charge capacity.
LCD name
Modbus address
Bat. SoC <25%
0x4016
Value 1
Value 2
Inactive (0), Active (1)
Not used
8
Battery over discharge current
Active when the measured battery discharge current reaches the threshold specified in "Battery max.
discharge current" field (see no. 11 in section 6.2).
LCD name
Modbus address
Bat. over discharge I
0x4017
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Max. measured value
9
Battery low
Active when the measured battery voltage is under the threshold specified in "Battery low voltage"
field (see no. 9 in section 6.2).
LCD name
Modbus address
Bat. low
0x4018
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Min. measured value
10
Battery deep discharged
Active when the battery measured voltage is under the threshold specified in "Battery deep discharge
voltage" field (see no. 10 in section 6.2).
LCD name
Modbus address
Bat. deep discharge
0x4019
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Min. measured value