6.4
Logs
Every event is logged in the device flash memory. From the log menu the user can view their history. Use
the UP/DOWN keys to navigate between logs, 2 logs are visible simultaneously on the LCD.
Figure 15 Log Screen
1.
Time:
time at which the log occurred
2.
Date:
date at which the log occurred
3.
Name:
unique log name
4.
Primary value:
optional, see below for details
5.
Secondary value:
optional, see below for de-
tails
Logs are of 3 different kinds:
info
,
alarms
and
events
. All info and alarms have an associated Modbus
field representing the current status (0 if inactive or 1 if active). For info and alarms a log is generated at
each status transaction. In case of active alarm, the front LED and the buzzer turn ON.
6.4.1
Info
1
Battery charging
Active when the battery is charging.
LCD name
Modbus address
Bat charging
0x4000
Value 1
Value 2
Inactive (0), Active (1)
Not used
2
Battery floating
Active when the battery is fully charged.
LCD name
Modbus address
Bat floating
0x4001
Value 1
Value 2
Inactive (0), Active (1)
Not used
3
Battery discharging
Active when the battery is discharging.
LCD name
Modbus address
Bat. discharging
0x4002
Value 1
Value 2
Inactive (0), Active (1)
Not used
4
USB powered
The UPS module is powered by USB only.
LCD name
Modbus address
USB powered
0x4020
Value 1
Value 2
Inactive (0), Active (1)
Not used