6.3
Info menu
While in the info menu, use the UP/DOWN key to navigate through the menu items. The fields are also
accessible via Modbus at the specified address. Modbus device identification fields are read using func-
tion 43/13 (0x2B/0x0E) at the specified object id.
1
Firmware version
3.3 digit indicating the firmware major minor version
LCD name
Modbus
FW version
Device Identification Object Id 0x02
2
Firmware subversion
3 digit indicating the firmware subversion.
LCD name
Modbus
FW subversion
Device Identification Object Id 0x80
3
Build date
Firmware build date.
LCD name
Modbus
Build date
Device Identification Object Id 0x82
4
Build time
Firmware build time.
LCD name
Modbus
Build time
Device Identification Object Id 0x83
5
Serial number
Device serial number.
LCD name
Modbus
S/N
Device Identification Object Id 0x81
6
Boot cycles
Counter of power ON cycles.
Unit
LCD name
Modbus address
Cycles
Boot cycles
0x2010
7
Operating time
Counter for operating hours of the UPS module.
Unit
LCD name
Modbus address
Hours
Operating time
0x2020
8
Battery operating time
Hours elapsed since the "Battery installation date" (see no. 41 in section 6.2).
Unit
LCD name
Modbus address
Hours
Bat. operating time
0x2022