5
|
Function description
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
20
Address Type
R/W
Unit
Min.
Max.
Description
0x1012
UINT16 R/W
0.1 A
0.5
20
Battery charge current
0x1013
UINT16 R/W
0.1 V
10
58
Battery float voltage
0x1014
UINT16 R/W
0.1 V
5
58
Battery low voltage
0x1015
UINT16 R/W
0.1 V
5
58
Battery deep discharge voltage
0x1016
UINT16 R/W
0.1 A
5
21
Battery max. discharge current
0x1017
UINT16 R/W
0.1 Ah 1
200
Battery capacity - Supercap capacitance
0x1018
SINT16 R/W
1 °C
-40
60
Battery min. temperature
0x1019
SINT16 R/W
1 °C
-40
60
Battery max. temperature
0x101A UINT16 R/W
1 kh
1
100
Battery lifetime
0x101B UINT16 R/W
1
0
3
Ri alarm mode
0: Disabled
1: Fix
2: Automatic
3: Automatic done
0x101C UINT16 R/W
0.1 m© 0
300
Ri nom
0x101D UINT16 R/W
1%
50
300
Ri max. variation
0x1020
UINT16 R/W
1
1
2
Operating mode
1: UPS
2: DC-DC
0x1021
UINT16 R/W
0.1
10
58
Nominal output voltage
0x1022
UINT16 R/W
0.1
5
21
Max. input current
0x1023
UINT16 R/W
0.1
1
21
Max. output current
0x1024
UINT16 R/W
1
0
1
Max. Backup time enable
0: Disabled
1: Enabled
0x1025
UINT16 R/W
1 m
1
1440
Max. backup time.
0x1026
UINT16 R/W
1
0
1
Buzzer enable
0: Disabled
1: Enable
0x1027
UINT16 R/W
1
0
65535 Relay 1 configuration (see no. 27 in section
0x1028
UINT16 R/W
1
0
65535 Relay 2 configuration (see no. 27 in section
0x1029
UINT16 R/W
1
1
2
Inhibit polarity
1: Low
2: High
0x102A UINT16 R/W
1
1
2
DC-DC output mode
1: Single
2: Parallel
0x102B UINT16 R/W
1
0
1
Output enable
0: Disabled
1: Enabled
0x102C UINT16 R/W
1
0
1
Aux enable
0: Disabled
1: Enabled
0x102D UINT16 R/W
1
0
1
Cold start on inhibit toggle
0: Disabled
1: Enabled
0x102E UINT16 R/W
1
0
1
Cold start on battery connection
0: Disabled
1: Enabled
0x1030
UINT16 R/W
1
0
1
PC shutdown enable