5
|
Function description
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
14
The charger voltage is independent on the input voltage (power supply), and is user settable.
Lead acid and lithium batteries share the same 3 stages charging algorithm as shown on Figure 7.
Figure 7 Lead acid and Lithium charging algorithm
For nickel batteries, during maintenance, the UPS module gives pulses of 3 s every 30 s with a maximum
current of 1/10 of the battery charge current and maximum voltage equal to the battery charge voltage.
Figure 8 Nickel charging algorithm
For Supercapacitor after the constant current phase the algorithm goes directly to maintenance keeping
the voltage at battery charge voltage.
Figure 9 Figure 7: Supercapacitors charging algorithm
Time
Current
Voltage
Constant current
Constant voltage
Maintenance
Charge current
Charge voltage
Float voltage
Time
Current
Voltage
Constant current
Constant voltage
Maintenance
Charge current
Charge voltage
Time
Current
Voltage
Constant current
Maintenance
Charge current
Charge voltage