background image

3

RH

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 2. Typical wiring diagram for

heat only,  3-wire, single transformer systems

TRANSFORMER

Heating

System

Fan

Relay

Y

C‡

RC

JUMPER

WIRE

O

B

For 2-wire Heat only, 
attach to RH and W

NOTE

RH

Y

24 VAC

120 VAC

Hot

Neutral

TRANSFORMER

THERMOSTAT

SYSTEM

G

W

Figure 3. Typical wiring diagram for

cool only, 3-wire, single transformer systems

Cooling
System

Fan

Relay

RC

O

B

C‡

JUMPER

WIRE

RH

Y

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 4. Typical wiring diagram for

heat/cool, 4-wire, single transformer systems

TRANSFORMER

Heating

System

Fan

Relay

Cooling
System

RC

JUMPER

WIRE

O

C‡

B

RED jumper wire (provided with thermostat) must be 
connected between thermostat RH and RC terminals 
for proper thermostat operation with this system.

NOTE

RH

Y

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 5. Typical wiring diagram for

heat/cool, 5-wire, two-transformer systems

HEATING

TRANSFORMER

Heating

System

Fan

Relay

Cooling
System

RC

24 VAC

120 VAC

Hot

Neutral

COOLING TRANSFORMER

O

B

C‡

RH

Y

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 6. Typical wiring diagram for heat pump

with reversing valve energized in COOL

TRANSFORMER

Reversing

Valve*

RC

O

B

C‡

JUMPER

WIRE

Compressor

Contactor

JUMPER

WIRE

* Reversing valve is energized when the
   system switch is in the COOL position

Fan

Relay

RH

Y

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

G

W

Figure 7. Typical wiring diagram for heat pump

with reversing valve energized in HEAT

TRANSFORMER

Reversing

Valve*

RC

O

B

C‡

JUMPER

WIRE

Compressor

Contactor

JUMPER

WIRE

* Reversing valve is energized when the
   system switch is in the HEAT position

Fan

Relay

The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year
with fresh "AA" Energizer

®

 alkaline batteries.

Heating System

Heating System

Heating System

Heating System

Heating System

1. Move SYSTEM switch to HEAT

HEAT

HEAT

HEAT

HEAT  position. If the heating

system has a standing pilot, be sure to light it.

2. Press 

 to adjust thermostat setting above room tempera-

ture. The heating system should begin to operate.

3. Press 

 to adjust temperature setting below room tem-

perature. The heating system should stop operating.

To prevent compressor and/or property damage, if the

To prevent compressor and/or property damage, if the

To prevent compressor and/or property damage, if the

To prevent compressor and/or property damage, if the

To prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operate

outdoor temperature is below 50°F, DO NOT operate

outdoor temperature is below 50°F, DO NOT operate

outdoor temperature is below 50°F, DO NOT operate

outdoor temperature is below 50°F, DO NOT operate
the cooling system.

the cooling system.

the cooling system.

the cooling system.

the cooling system.

1. Move SYSTEM switch to COOL

COOL

COOL

COOL

COOL position.

2. Press  

 to adjust thermostat setting below room tempera-

ture. The blower should come on immediately on high
speed, followed by cold air circulation

3. Press 

 to adjust temperature setting above room tem-

perature. The cooling system should stop operating.

Cooling System

Cooling System

Cooling System

Cooling System

Cooling System

!

CAUTION

CAUTION

CAUTION

CAUTION

CAUTION

Summary of Contents for 1F80-261

Page 1: ...on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not use on circuits exceeding specified voltage Do not...

Page 2: ...conditioning service person ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL ATTACH THERMOSTAT BASE TO WALL 1 Remove the pack...

Page 3: ...JUMPER WIRE Compressor Contactor JUMPER WIRE Reversing valve is energized when the system switch is in the HEAT position Fan Relay The 24 Volt neutral connection to terminal C on the thermostat is not...

Page 4: ...s RUN to make sure the thermostat is in the run program mode then press PRGM and RUN at the same time to enter the configuration menu The display will show the first item in the configuration menu The...

Page 5: ...mperature to match your previous thermostat 8 8 8 8 8 Select F or C Readout Select F or C Readout Select F or C Readout Select F or C Readout Select F or C Readout Changes the display readout to Centi...

Page 6: ...tures you want during each period Fill in the complete table to have a record of your programs Entering Your Program Entering Your Program Entering Your Program Entering Your Program Entering Your Pro...

Page 7: ...ion CorrectiveAction CorrectiveAction NoHeat NoCool NoFan NoHeat NoCool NoFan NoHeat NoCool NoFan NoHeat NoCool NoFan NoHeat NoCool NoFan 1 Blownfuseortrippedcircuitbreaker Replacefuseorresetbreaker c...

Page 8: ...rroworwidetemperatureswing oftheCoolingSystemmaybeinfluencingthe adjusted Contactalocalservicepersonfor cyclerate suggestions ThermostatSettingandThermometer ThermostatSettingandThermometer Thermostat...

Reviews: