Whisper Power WBM-Basic Owner'S Manual Download Page 1

High Precision Battery Monitor

Battery Monitor Basic

Owner’s manual

Thank you for purchasing a Whisper Power Battery

Monitor (WBM).

Please read this owner’s manual for information

about using the product correctly and safely.

Keep this owner’s manual close to the battery

monitor for future reference.

Whisper Power BV

Kelvinlaan 82, 9207 JB Drachten, The Netherlands

http://www.whisperpower.eu

1. WBM-Basic display and control overview

1. Charge battery indicator
2.
3.
4.
5.
6.
7.
8. Select State-of-charge readout, or n
9. Select current (A) or Amphour (Ah) readout, or enter / leave Setup menu
10. Select voltage readout (Main or Auxiliary), or previous value (<)

Alarm activated indicator
Numeric value indicator field
Readout units
Main battery or Auxiliary battery indicator
State-of-charge bar
Synchronize indicator

ext value (>)

2. Synchronisation

In order to keep your battery monitor delivering accurate status information about your
battery, it is important to regularly synchronize your battery monitor with your battery. As
explained in the quick start guide, a synchronisation step is also needed before you can
actually use your battery monitor. During operation, the battery monitor automatically
indicates when a synchronisation is required, by displaying the message SYNCHRONIZE.

Performing synchronisations regularly is also important to keep your battery healthy and to
increase it’s lifetime. You will notice that if you are often performing full charge cycles
yourselves, the battery monitor will most likely not display the SYNCHRONIZE message,
since the battery is already kept in good sync with the battery monitor.

Besides automatic synchronisations based on meeting the Auto-Sync Functions, you can
also manually synchronize the battery monitor with your battery when you are sure your
battery is fully charged. This can be accomplished by pressing both < and > keys
simultaneously for three seconds. After these three seconds, the flashing FULL message
appears on the the display just like when it is automatically synchronized.

A synchronisation step means nothing more than performing a

charge cycle on

your battery. A charge cycle will be considered complete when all discharged energy is
restored in the battery and both Auto-sync parameters  F02 and F03 are met during at
least 4 minutes. This typically means : when the battery charger switches to float mode. By
meeting these conditions, the battery is considered full, which will be indicated by a
flashing FULL message on the display. Besides this, the State-of-charge readout will be
set to 100% and the Amphour readout reset to 0Ah. The FULL message will disappear
when a key is pressed, or automatically, when the battery starts discharging again.

complete

Before proceeding with this owner’s manual, please make
sure you have carefully read the enclosed installation guide as

well!

3. Setup menu

Using the Setup menu, your battery monitor can be adjusted to fit into your system. A
number of parameters, called Functions, can be set according to your needs. This menu
can be accessed by the following sequence :

When the Setup menu is entered, you can use the < and > keys to browse through the
different Functions. By pressing the SETUP key, the selected Function value can be
viewed. The < and > keys can now be used to change this value. Pressing the SETUP key
again, will then step back to the Setup menu. From any menu position, the Normal
Operating Mode can be accessed again by pressing the SETUP key for 3 seconds. This
will also save any Function value changes to internal memory. When no keys are pressed
for 90 seconds while operating in the Setup menu, the battery monitor will automatically
return to the Normal Operating Mode again without saving any Function value changes.

The following Functions are available :

The factory settings are based on a 12V battery system with a capacity of 200Ah. For 12V
systems, generally only Function F01 has to be checked for correct operation of your
battery monitor. When your battery capacity is other than 200Ah, Function F01 has to be
changed to a value that is equal to your battery capacity. All other Functions can be left
unchanged if you are uncertain about adjusting these values yourselves.

When your battery system is 24V, besides checking battery capacity Function F01 for the
correct value, you should also change the values of F02 and F05. Default 24V system
values for F02 and F05 are respectively 26.4V and 21.0V.

F02

Charger's float voltage (

. This value must be equal to your

battery charger’s float voltage. which is the last stage of the charging process. In
this stage the battery is considered full.

Auto-sync parameter)

Default : 13.2V

Range : 8.0V - 33.0V

Step size : 0.1V

F03

Charger's float current (Auto-sync parameter). When the charge current is below
this percentage of the battery capacity (see Function F01), the battery will be
considered as fully charged. Make sure this Function value is always greater than
the minimum current at which the charger maintains the battery or stops charging.

Default : 2.0%

Range : 0.5 - 10.0%

Step size : 0.1%

F04

Low battery alarm On (% SOC). When the

percentage has fallen

below this value, the alarm relay will be activated,

State-of-charge

the Charge battery indicator

starts flashing and the State-of-charge bar is empty.

Default : 50%

Range : 0 - 99%

Step size : 1%

F05

Low battery alarm On (Volts). When the

has fallen below this

value, the alarm relay will be activated.

battery voltage

Default : 10.5V

Range : 8.0 - 33.0V

Step size : 0.1V

F06

Low battery alarm Off (% SOC). When the State-of-charge percentage has risen
above this value and the alarm relay was activated, the alarm relay will deactivate
again. When “FULL” is selected, the alarm relay is deactivated when the Auto-
sync parameters are met.

Default : 80%

Range : 1 - 100% / FULL

Step size : 1%

EN

2

3

4

5

6

7

8

F01

Battery capacity. Your Main battery’s capacity in Amphours (Ah).

Default : 200Ah

Range : 20 - 999Ah

Step size : 1Ah

F07

Peukert's exponent. The Peukert’s exponent represents the effect of reducing
battery capacity at higher discharge rates. When the Peukert value of your battery
is unknown, it is recommended to keep this value at 1.25. A value of 1.00 disables
the Peukert compensation.

Default : 1.25

Range : 1.00 - 1.50

Step size : 0.01

F08

Shunt Amp Rating. This Function represents the Amp rating of your shunt at
50mV. Included with your battery monitor is a 500Amp/50mV shunt, meaning that
at 500A flowing through the shunt, a voltage of 50mV is generated across the
small ‘Kelvin’ screw terminals of the shunt. This voltage will be used by the battery
monitor to measure the amount of current.

Default : 500A

Range : 10 - 900A

Step size : variable

F09

Backlight mode. Represents the duration of backlight activation in seconds after
key-press. The backlight can also be set to be always “ON” or always “OFF”.
Function setting “AU”, activates the backlight automatically when charge /
discharge current exceeds 1Amp or when a key is pressed.

Default : 30sec

Range : OFF / 5

300 / ON / AU

Step size : variable

F10

Alarm contact polarity. Enables selection between a normally open (NO) or
normally closed (NC) contact.

Default : NO

Range : NO / NC

F11

Reserved

Default : x

Range : x

F12

Firmware version. Displays the firmware version of the battery monitor (read only).

Default : x.xx

r.b

Reset Battery status. Use this reset item to reset your current battery status, for
example after you have installed a fresh battery of the same specifications as the
previous one.

r.F

Reset Functions. This reset item can be used to reset all Function values to
factory default values.

The last two Functions are socalled Reset Functions. By pressing the SETUP key the
selected Reset Function can be viewed. The default value for all Reset Functions is

OFF

.

To actually reset the selected Function, use the < and > keys to change the value from

OFF

to

ON

. Pressing the SETUP key again, will step back to the Setup menu. All reset

items set to

ON

will only be reset once the Normal Operating Mode is accessed again by

pressing the SETUP key for 3 seconds. The following Reset Functions are available :

Whisper Power (WP) warrants this product to be free from defects in workmanship or
materials for 24 months from the date of purchase. During this period WP will repair the
defective product free of charge. WP is not responsible for any costs of the transport of
this product.

This warranty is void if the product has suffered any physical damage or alteration, either
internally or externally, and does not cover damage arising from improper use or from use
in an unsuitable environment.

This warranty will not apply where the product has been misused, neglected, improperly
installed or repaired by anyone other than WP. WP is not responsible for any loss, damage
or costs arising from improper use, use in an unsuitable environment or improper
installing, setup and malfunctioning of the product.

Since WP cannot control the use and installation (according to local regulations) of their
products, the customer is always responsible for the actual use of these products. WP
products are not designed for use as cricital components in life support devices or
systems, that can potentially harm humans and/or the environment. The customer is
always responsible when implementing WP products in these kind of applications. WP
does not accept any responsibility for any violation of patents or other rights of third
parties, resulting from the use of the WP product. WP keeps the right to change product
specifications without previous notice.

Examples of improper use are :

- too high input voltage applied
- wrong shunt connection
- applying battery voltage to shunt input
- mechanically stressed enclosure or internals due to harsh handling and/or incorrect

packaging

- contact with any liquids or oxidation caused by condensation

1)

1)

4. Warranty conditions

6. Declaration of conformity

MANUFACTURER

:

Whisper Power BV

ADDRESS

:

Kelvinlaan 82
9207 JB Drachten
The Netherlands

Declares that the following products :

PRODUCT TYPE

:

BATTERY MONITOR

MODEL

:

WBM-Basic

Conforms to the requirements of the following Directives of the European Union :

EMC Directive 2004/108/EC

The above product is in conformity with the following harmonized standards :

EN61000-6-3: 2001

EMC - Generic Emissions Standard

EN61000-6-2: 2005

EMC - Generic Immunity Standard

RoHS Directive 2002/95/EC

5. Technical specifications

Parameter

WBM-Basic

Supply voltage range

Supply current

:

@Vin=24VDC

1)

Input voltage range (auxiliary battery)

Input voltage range (main battery)

Input current range

2)

Battery capacity range

Operating temperature range

Readout resolution :

voltage (0..35V)

current (0..100A)

current (100..999A)

amphours (0..99Ah)

amphours (100..999Ah)

@Vin=12VDC

9..35VDC

7mA

9mA

2..35VDC

0..35VDC

-999..+999A

20..999Ah

-20..+50°C

± 0.1V

± 0.1A

± 1A

± 0.1Ah

± 1Ah

1)

2)

Measured with backlight and alarm relay turned off.
Depends on selected shunt. With standard delivered 500A/50mV shunt (350A

continuous), the  range is limited to -600..+600A.

Note: the given specifications are subject to change without notice.

- WBM professional connection kits

lengths : 6m, 12m

- WBM quick connection kits

lengths : 3m

Accessories

weight

Protection class

145 grams

IP20 (frontpanel only IP 65)

height

17mm (base) / 35mm (M8 screws)

Weight

Shunt dimensions :

footprint

95grams

45 x 87mm

total depth

79mm

Dimensions :

frontpanel

body diameter

ø 64mm

ø 52mm

Current measurement accuracy

± 0.4%

state-of-charge (0..100%)

Voltage measurement accuracy

± 0.1%

± 0.3%

1

9

10

[3 sec]

WBM-Basic Manual Rev1en / Printed in The Netherlands

Reviews: