   Display Mode Description:

Ÿ

  Apply Power.

Ÿ

  The power on sequence will illuminate all 

LEDs on the front panel.

Ÿ

  The Software Revision is then displayed in 

the lower right hand display.

Ÿ

  Mode A Voltage (blue LED) and current 

measurements will display.

  Mode A Voltage Display (blue LED reference)

 

     The TOP row of displays will show (left to right):

Ÿ

  X Leg to Neutral voltage

Ÿ

  Y Leg to Neutral voltage

Ÿ

  Z Leg to Neutral voltage

Ÿ

  Safety Ground to Neutral voltage

   Mode B Voltage Display (red LED reference)

       The TOP row of displays will show (left to right):

Ÿ

  X-Leg to Y-Leg voltage

Ÿ

  Y-leg to Z-Leg voltage

Ÿ

  Z-Leg to X-Leg voltage

Ÿ

  Frequency

   Amperage Display (mode A and B)

        The bottom row of displays will always show:

Ÿ

  X-Leg current

Ÿ

  Y-Leg current

Ÿ

  Z-Leg current

Ÿ

  Neutral Leg current

   Flashing Display Notifications

          The Voltage displays will flash when a voltage  

  

is out of range.

Ÿ

    In Mode A, the X, Y, or Z to Neutral voltage 

display will flash when the voltage is below 
108 Volts or above 131 Volts.

Ÿ

    In Mode B, a voltage display will flash when 

the voltage is less than 187 Volts or greater 
than 228 Volts.

Theory of operation: Voltage Measurement:

The first 3 of 4 Voltage displays are the primary voltage 
measurements. Normal use is expected to be 3 phase “Y” 
with three 120 Volt AC Legs or single phase with two hot 
Legs.  It also measures Leg to Leg voltages of 208 Volts 
AC. Maximum voltage Leg to Neutral or Leg to Leg is 280 
Volts AC.

The PL-PM1 also measures Neutral to Ground voltages 

th

(4  display, normal mode). The range on the Neutral to 
Ground is 0 to 99 Volts AC.
Accuracy is better than 2%, typically 1%. 

The Voltage Input connector is a Wago 5 pin model with 
the center pin (safety ground) designed to mate first, due 
to a longer pin. 
The connections are (Left to Right looking at the rear of 
the chassis)
       1.  X- Leg

 2.  Y-Leg
 3.  Safety Ground (extended pin)
 4.   Z- Leg
 5.  Neutral

Current Measurement:

Current measurement utilizes 4 Current Transformers part 
# TRCT600:1. The PL-PM1 presents a 1.5 Ohm resistive 
load to the current transformer. It has a 600 to 1 current 
ratio. At 400 Amps AC in, the coil delivers 0.66 Amps AC. 
The maximum current the PL-PM1 measures is 400 Amps 
AC.

Accuracy is better than 2%, typically 1%.

The Current Input connector is an 8 pin Wago to the PL-
PM1 from the current transformers.
The connections are:
 

1,2:  

X-Leg current loop

 

3,4: 

Y Leg current loop

 

5,6: 

Z-Leg current loop

7,8: 

Neutral Leg current Loop

Polarity of the current loop inputs does not matter, 
although it is recommended to connect the red and black 
in a consistent fashion on all the coils.

For technical assistance:

whirlwind

99 Ling Road - Rochester, New York 14612
800-733-9473 / 585-663-8820   Fax: 585-865-8930
whirlwindusa.com    Made in U.S.A.

Changing the PL-PM1RJ IP address

There are two methods of accessing the PL-PM1RJ to change the IP address.

1)  Use a router to establish a small temporary network at 192.168.1.1.

       2)  Use a cross wired cable or two straight cables with a switch to directly connect a computer to the meter's 

network connection jack.

Using a Router to set IP address

With the computer connected to the router, access the setup for the router.
Set the router to have an IP address 0f 192.168.1.1 and subnet mask of 255.255.255.0.
Connect the PL-PM1RJ to the router.
Type the IP address 

into a browser on the computer to connect to the meter. Note that the PL-

http://192.168.1.200 

PM1RJ also responds to ping commands.

When the browser window with the meter display opens, click on the Setup button in the lower right corner. To change 
the IP address, simply type the new IP address and Subnet Mask in the boxes, check for accuracy, and click Apply. 
The unit can also be given an identifying name in this screen as well. Once set internally, the system will try to contact 
the unit at the new address.

To confirm the IP address, press and hold the mode button for more than 3 seconds, and, the IP address will appear 
in the top row of LED number displays and the subnet mask will appear in the lower row of numbers.  Press the mode 
button again to exit this mode.

Note that for subsequent IP changes you must connect to the meter using its current address and the router must be 
set correspondingly. The router IP right set of digits should always be lower than the computer and the meter settings.

Using a cross wired cable or Ethernet switch to change IP address

Using a cross wired Ethernet cable, connect a computer to the PL-PM1RJ. Using a web browser, type the IP address 
PL-PM1RJ into address bar of the browser. The default address for the meter is 192.168.1.200. Allow time for the 
computer to find the unit and open it in the browser window. This method also applies to using a switch with two 
standard Ethernet cables to connect to the PL-PM1RJ.

When the browser window with the meter display opens, click on the Setup button in the lower right corner. To change 
the IP address, simply type the new IP address and Subnet Mask in the boxes, check for accuracy, and click Apply. 
The unit can also be given an identifying name in this screen as well. Once set internally, the system will try to contact 
the unit at the new address.

Supported Web Browsers

Google

 Chrome

 No known issues 

with recent versions.
Mozilla

 Firefox

® (v34) sometimes 

requires multiple refreshes at 
startup. Pop-up lists do not appear 
in correct spot. It is a zoom issue.
Microsoft

 Internet Explorer

 No 

known issues with v11. Possible 
issues with v10. Previous versions 
do not work.
Apple

 Safari 

No known issues.

Tests were conducted with:
Apple iPad 2
Apple iPhone 4s
Windows IE 11
Windows Chrome 38.
Windows Firefox 33
Apple Safari 7.1
Apple Chrome 38.0.2125.104
Apple Firefox 32.03

(Standard Android browsers are 
not supported. Readings may be 
inaccurate)

The display below shows the  
compact display view with the 
setup page activated.

Personalizing Display Features

The PL-PM1RJ has a Display 
Parameters menu that allows for 
display color changes and the setting 
of alerts to indicate out of range 
voltage readings. The meter reading 
refresh rate can also be changed on 
this screen. These settings are 
stored as cookies in the web 
browser, so they are specific to the 
individual computers accessing the 
PL-PM1RJ.

MODEL NUMBERS
PL-PM1RJ with network 
interface
PL-PM1 without network 
interface

whirlwind 

PL-PM1RJ Power Meter 

whirlwind

whirlwindusa.com 

Whirlwind PL-PM1/PL-PM1RJ Power Meter Technical Information.

Intended Use:

The Whirlwind PL-PM1/PL-PM1RJ Power Meter is intended to monitor 3 phase Y power with three 120 Volt AC 
legs or single phase with two 120 Volt AC legs. It is intended to monitor the line side voltage and load current of 
both portable AC distribution and permanent power distribution systems.