Wheelock RMS-3R Installation Instructions Download Page 1

P83542 B 

Sheet 1 of 5 

 

273 Branchport Avenue 
Long 

Branch, 

NJ 

 

07740 

         

 

Thank you for using our products. 

(732)  222-6880 

INSTALLATION INSTRUCTIONS 

REMOTE MICROPHONE (DUAL CIRCUIT) 

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

 
 

MODEL NUMBERS: 
 

       RMS-3B 

 

 

   Remote 

Microphone 

Dual 

Circuit 

Black 

 

       RMS-3R 

 

 

   Remote 

Microphone 

Dual 

Circuit 

Red 

                

 
 
GENERAL: 

The Remote Microphones are UL Listed under Standard 864, Control Units for Fire-Protective Signaling Systems. 

They are Listed 

for indoor use only

.  The Remote Microphone is designed to be used with Wheelock’s Dual Zone SAFEPATH Panel model DCSP.  

It provides a means for making emergency voice announcements from an auxiliary location.   Only 1 Remote Microphone can be 
connected to the SAFEPATH Panel.  The hand held push to talk microphone is supervised to ensure proper connection.  It is not 
replaceable.  If it is detached from the unit, the unit must be returned for repair. 
 

READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. 

 
 

SPECIFICATIONS: 

 

Power Input Voltage:    20-31VDC 
Audio Output Level:     1.05V RMS 
Output Impedance:        600 Ohms 
Input 

Current:     50mA 

 
 

WIRING DIAGRAM: 

 

 

 

Figure 1. 

 

 

WIRING SPECIFICATIONS: 

 

Cable Size:              14 - 22 AWG Shielded.  The shield must be connected only at the SAFEPATH Panel. 
Maximum 

Length: 

   1000 

Feet 

Maximum Capacitance:   .05uF/Total Run (50pF/foot for 1000 FT.) 

 

Copyright 1997, 1998 Wheelock, Inc.  All rights reserved. 

 