Pro-Guard & Uni-Guard Installation Manual
20
FLOW CHART OF SUGGESTED TUNING PROCEDURES
System Defaut
Weak Performance & or False alarms
from your systems or theirs
Check Noise "D"
D
B
Alternate betw een D1-D2 & B to
get most favorable parameters
( Low Noise Level )
If noise is less than 80
If noise is very high (eg. more than hundreds)
H
A
If OK - You are done
If noise is very high
1/2 of new noise or less=value
than several hundred
increase slightly if False Alarms
Adjust Gain to 0
IF Not Acceptable
Check Noise Value and
Sensitivity of the System .
C
H
If system is picking w ell,
Adjust until sensitive enough
Your'e Done, If w eak
then increase until stable
adjust H to approximately
1/2 of Noise Level, if false
alrarms adjust slightly
Upw ard
C
Adjust from C6 to C1
until system is w orking
w ell. Than adjust Up
until system is stable
*Alw ays Watch the system for about an Hour to ensure that you have chosen stable paramaters