whl-648 Rev. 001 Rel. 003 Date 10.8.19
39
Part 7 - Connecting Electrical Service
WARNING
!
ELECTRICAL SHOCK HAZARD – To ensure safety, turn off electrical
power supply at service entrance panel before making any
electrical connections to avoid possible electric shock hazard.
Failure to do so could result in property damage, serious personal
injury, or death.
Jumping out control circuits or components WILL VOID product
warranty and can result in property damage, personal injury, or
death.
Install wiring and electrically ground boiler in accordance with
the authority having jurisdiction or, in the absence of such an
authority, follow the National Electrical Code, NFPA 70, and/or
CSA C22.1 Electrical Code-Part 1 in Canada. Failure to follow all
applicable local, state, and national regulations, mandates, and
building supply codes for guidelines to install the electrical power
supply could result in property damage, serious personal injury,
or death.
A. Wiring
The boiler is equipped with a three prong power cord. The boiler is
limited to a maximum of 15 amps at 120 volts in use.
It is of extreme importance that this unit be properly grounded. It
is very important that the building system ground is inspected by
a qualified electrician prior to making this connection. Electrical
power must only be turned on when the boiler is completely filled
with cold water. Failure to follow these instructions could result in
component or product failure, serious injury, or death.
CAUTION
!
Label all wires prior to disconnecting them when servicing the
boiler. Wiring errors can cause improper and dangerous operation.
Failure to follow these instructions may result in property damage
or personal injury.
Figure 31 - Proper Grounding - Internal Manual Power Switch
1. This boiler must be properly grounded. Ensure the electrical
receptacle is properly grounded. Do not remove the grounding prong
from the boiler plug.
2. Do not attach the ground wire to either the gas or water piping.
3. The wiring diagrams in this manual are to be used for reference
purposes only.
4. Refer to these diagrams and the wiring diagrams of any external
controls used with the installation when wiring the boiler. Read,
understand, and follow all wiring instructions supplied with the
controls.
5. Do not disconnect the power supply when the boiler is in normal
operation.
NOTE:
For additional electrical protection, the use of a whole house
surge protector is recommended. Damage caused by power surges IS
NOT covered by the warranty.
NOTICE
If the boiler display does not turn on, first check the plug. Then check
the electrical panel circuit breaker and reset if necessary. If the circuit
breaker trips again, do not reset. Disconnect the plug and have a
qualified technician diagnose the problem.
B. Dip Switches
There is one set of DIP switches. DIP switches 6 and 7 need to be set to
OFF for the boiler to operate normally.
Figure 32 - Proper Grounding - Internal Manual Power Switch
DIP SWITCH
OFF
ON
1-3
Factory
Factory Settings - DO NOT CHANGE
4
Vent Size
2”
3”
5
Gas Type
LP
NG
6
High Fire
Normal
High Fire
7
Low Fire
Normal
Low Fire
Table 19 - DIP Switch Group - NOTE: DO NOT CHANGE SWITCHES 1-3.
THESE ARE FACTORY SETTINGS.
Maximum Flame Detecting Voltage
2.4V
Pre-Purge Time (Tp)
Maximum 10 seconds,
Minimum 1 second
Safety Time (Igniting Time) (Ts)
3.5 seconds
Igniting Interval Time
20 seconds
Post-Purge Time (Tip)
3 minutes
Over-Heating 1, 2, 3, Protection
Detection Time
<3 seconds
Pump 1 Post Circulating Time (T1pv)
1 minute
Pump 2 Post Circulating Time (T2pv)
1 minute
High and Low Water Level Detection
Time
<6 seconds
High and Low Water Level Recovery
Time
<6 seconds
Table 20 - System Control Settings
Summary of Contents for WBRC 140 Series
Page 21: ...whl 648 Rev 001 Rel 003 Date 10 8 19 21 E Applications Figure 10 Piping Symbol Legend ...
Page 40: ...whl 648 Rev 001 Rel 003 Date 10 8 19 40 Figure 33 Electrical Wiring Diagram ...
Page 41: ...whl 648 Rev 001 Rel 003 Date 10 8 19 41 Figure 34 Ladder Diagram ...
Page 81: ...whl 648 Rev 001 Rel 003 Date 10 8 19 81 Notes ...
Page 82: ...whl 648 Rev 001 Rel 003 Date 10 8 19 82 This Page Intentionally Left Blank ...
Page 83: ...whl 648 Rev 001 Rel 003 Date 10 8 19 83 This Page Intentionally Left Blank ...