73
WHL-016 REV. 12.18.14
NOTE:
The boiler will automatically exit test mode after 20 minutes of operation.
COMBUSTION SETTINGS ON ALL MODELS
Natural Gas
Propane LP
Fan Speed
Low
Ignition
High
Low
Ignition
High
Carbon Monoxide PPM
5
– 50
60 - 100
< 150
5
– 50
60 - 100
< 150
Carbon Dioxide (CO
2
)
8 - 10%
8 ½ - 10 ½%
8 ½ - 10 ½%
9 - 10 ½%
9 ½ - 11%
Table 27
FAN SPEEDS
MODEL
IGNITION
MIN
MAX
055
3800
1650
4050
080
3800
1850
5000
110
3800
1850
6050
155
4100
1850
5400
199
3800
1750
6050
285
4600
1800
6050
399
4200
1900
6950
Table 28
PART 12 – SHUTDOWN
A. SHUTDOWN PROCEDURE
If the burner is not operating, disconnect the electrical supply.
If the burner is operating, lower the set point value to 70
o
F and wait for the burner to shut off. Continue to wait for the combustion
blower to stop, so all latent combustion gases are purged from the system. This should take a maximum of 40 to 90 seconds.
B. VACATION PROCEDURE
If there is danger of freezing, change the set point to 70
o
F. DO NOT turn off electrical power. If there is no danger of freezing, follow
“Shutdown Procedure”.
C. FAILURE TO OPERATE
Should the burner fail to light, the control will perform two more ignition trials prior to entering a lockout state. Note that each
subsequent ignition trial will not occur immediately. After a failed ignition trial, the blower must run for approximately 10 seconds to
purge the system. Therefore, a time period of approximately 40 to 90 seconds will expire between each ignition trial.
If the burner lights during any one of these three ignition trails, normal operation will resume. If the burner lights, but goes off in about 4
seconds, check the polarity of the wiring. See electrical connection section.
If the burner does not light after the third ignition trial, the control will enter a lockout state. This lockout state indicates that a problem
exists with the boiler, the controls, or the gas supply. Under such circumstances, a qualified service technician should be contacted
immediately to properly service the boiler and correct the problem. If a technician is not available, depressing and holding the RESET
button for more than 1 second will remove the lockout state so additional trials for ignition can be performed. The unit will try to re-light
once every 6 minutes.
SERVICE RUN
3400 RPM
PUMP ON
4:49P
Summary of Contents for WBCNG399W
Page 14: ...14 WHL 016 REV 12 18 14 SPECIFICATIONS AND DIMENSIONS Figure 2 Specifications and Dimensions ...
Page 24: ...24 WHL 016 REV 12 18 14 Figure 8 Piping Symbol Legend ...
Page 59: ...59 WHL 016 REV 12 18 14 Figure 32 Cascade Master and Follower Wiring ...
Page 60: ...60 WHL 016 REV 12 18 14 Figure 33 Internal Connection Diagram LP 293 J ...
Page 83: ...83 WHL 016 REV 12 18 14 055 080 110 PARTS BREAKDOWN Figure 36 Replacement Parts LP 387 J ...
Page 85: ...85 WHL 016 REV 12 18 14 155 199 285 399 PARTS BREAKDOWN ...
Page 86: ...86 WHL 016 REV 12 18 14 Figure 38 Replacement Parts LP 387 KK ...
Page 87: ...87 WHL 016 REV 12 18 14 155 199 285 399 MODEL PARTS BREAKDOWN ...
Page 91: ...91 WHL 016 REV 12 18 14 ...
Page 92: ...92 WHL 016 REV 12 18 14 ...