Westinghouse GCA series Instructions Download Page 1

Westinghouse 

I.L. 

15-825-14A 

TYPE  GCA  SIZE  5 

AC  CONTACTOR 

2  OR  3  POLES 

DESCRIPTION 

Fig. 

(Photo  BD  70-0584) 

Complete  Linestarter  Assembly  with  Type  GCA-530  Con­

tactor,  Type 

L-56 

Electrical  Interlock, 

Current  Trans­

formers  and  Type  A  Thermal  Overload  Relay. 

The  Type  GCA  Size 

AC  Contactor  is  completely 

assembled  on  an  insulated  base  of  molded  glass-poly­

ester.  It  is  suitable  for  mounting  on  either  steel  or 
insulating  panels.  Contactors  are  available  in 

or 

pole  front  connected  assemblies.  A  I inestarter  assem­

bly,  see  Fig.  CD,  incorporates  integrally  mounted 

current  transformers  and  overload  relay. 

This  unit  is  supplied  with  an  AC  operating  magnet. 

The  operating  coils  are  designed  for  continuous  duty 
from 

85% 

to 

110% 

of  rated  voltage. 

The  contact 

ratings  are  listed  in  Fig.®. 

Characteristics 

Open 

Enclosed 

Voltage  Rating 

600 

600 

8-hour  rating,  Amperes 

300 

270 

Fig. 

-

Ratings 

FRONT  CONNECTED 

The  main  contacts  are  of  the  bridging  or  double  break 
type.  Both  moving  and  stationary  contacts  are  faced 

with  a  silver  alloy,  whose  surfaces  are  kept  clean  by 

a  rolling  and  wiping  action  as  the  contacts  seal. 

Stainless  steel  compression  springs  in  each  moving 

contact  assembly  insure  adequate  contact  force  while 

providing  resilience  to  allow  for  contact  wear. 

The  arc  box  provides  a  mechanical  stop  for  the  mov­
ing  contact  assembly  and  maintains  the  proper  open 

contact  gap.  In  addition,  the  arc  box  contains  De-ion® 
arc  quenchers  which  draw  the  arc  away  from  the  con­
tacts  at  opening  and  produce  a  rapid  and  confined  arc 

interruption.  Twin  kick-out  springs  insure  positive 

drop-out  of  the  armature  assembly  when  the  coil 

is  de - energized. 

INSTALLATION 

Before  mounting  and  wmng,  the  desired  acces�ories 

such  as  electrical  interlocks,  mechanical  interlocks, 

current  transformers  and  overload  relays  should  be 

mounted  on  the  Type  GCA  Size 

AC  Contactor  or 

Line starter  assembly. 

The  assembly  should  then  be  mounted  with  four 

5/16" 

dia.  bolts.  Mounting  dimensions  are  shown  in  Fig.@ . 

.50 

LOAD 

CONNECTORS 

(17 f32• 

DIA 

HOLES! 

775 

Fig. 

. 38 1.5012 

MOUNTING SLOTS) 

3/8' 

DIA.  OPEN  END 

MOUNTING  SLOT 

12 

PLACES, 

(From  Dwg.  4808663) 

Type  GCA  Size 

AC  Contactor  Outline 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for GCA series

Page 1: ...ed with a silver alloy whose surfaces are kept clean by a rolling and wiping action as the contacts seal Stainless steel compression springs in each moving contact assembly insure adequate contact force while providing resilience to allow for contact wear The arc box provides a mechanical stop for the mov ing contact assembly and maintains the proper open contact gap In addition the arc box contai...

Page 2: ...ar with the hardware provided For proper interlock operation when the contactor is fully closed the interlock push rod can be manually depressed 06 1 16 inch further If adjustment is necessary the sIot in the end of the operator should be opened or closed to obtain this 06 1 16 inch Interlock Style No Ll Style No lor Interlock Kit Pole Interlock Includes Interlock Unit Mountlnc Combination Unit On...

Page 3: ...quipment its storage delivery installation check out safe opera tion or maintenance Care must be exercised to comply with local state and national regulations as well as safety practices for this class of equipment Arc Box The arc box provides the mechanical stop for the mov ing contact assembly while maintaining the proper open gap for the main contacts The molded box also supports the De ion r t...

Page 4: ...ise the crossbar into its proper position with the moving contacts inside the arc box 8 Replace the arc box on the contactor and secure ly tighten both mounting bolts Make sure both kickout springs are properly seated 9 Reconnect the leads to the new coiI Move cross bar by hand and make sure it moves freely with no mechanical friction RENEWAL PARTS I L 15 825 14A Photos 80 72 0008 and BD 72 0009 L...

Reviews: