Installation Guide
1. Overview
1.6 Performance Specifications
1.6
Performance Specifications
Table 5:
Performance Specifications
Specification
Value
Number of Drive Slots
102
Data Transfer Rates
12GBps SAS / 6Gbps SATA
Max Raw Data Storage Capacity
1.428 PB using 14TB HGST Ultrastar® HC530 drives
SAS Ports
12
x
Mini-SAS HD (6 per IOM)
2
x
10/100/1G Ethernet
1.7
Ultrastar Data102 Rack Requirements
The Ultrastar Data102 is designed to be installed into a rack that meets the EIA-310 standard at a minimum
1181-1197 mm (46.5in. - 47.13in.) of usable rack space, frame to frame. The vertical rack rails must be set
between 812.8mm - 914.4mm / 32 in. - 36 in. to support the enclosure. It requires 4U of rack space, and it
should be installed into the rack at the lowest possible U height to keep the load on the rack balanced.
Table 6:
Required Rack Specifications
Parameter
Requirement
Rack Depth
1181-1197 mm (46.5in. - 47.13in.) of usable rack space, frame to frame
Rack Width
450mm with (17.72in.) with 465mm (18.31in.) ± 1.5mm
nominal hole spacing. See EIA-310 Rack Standard
Rack Units (U)
4U
Vertical Rack Rail Spacing
812.8mm - 914.4mm / 32 in. - 36 in.
Static Load Rating
1360.7 kg. / 3000 lbs.
Dynamic Load Rating
1020.5 kg. / 2250 lbs.
Warning:
When extended out of the rack on the rail system, the Ultrastar Data102 will be
~950 mm / 37.4in. extended outward. This may be a potential tipping hazard depending on
the configuration of the rack. Ensure that leveling feet, anti-tilt, and any other safety features
recommended by the specific rack manufacturers have been deployed before servicing.
The following section provides specific information necessary to install, service, and remove the Ultrastar
Data102 . The installation of the Ultrastar Data102 requires two people and a space of 1524mm / 60in.
in front of the installation space. The servicing of the enclosure requires one person and a minimum of
1219.2mm / 48in. of space in front of the installation space. The removal of the enclosure requires two
people, 1371mm / 54in. of space in front of the installation space, and 24in. on either side of the enclosure
for two people to remove the enclosure.
6