ActiveScale™ P100 Support Guide
48
12. Verify that the settings on the System Interconnect match your configuration file.
3.3 Storage
Node
part
replacement instructions
The following sections provide information about Storage Node part replacement.
3.3.1 Replacing 3.5 inch drives
Table 3-16. 3.5 HDD replacement overview
3.3.1.1 Drive replacement guidelines
When replacing drives, do not:
• Install 12 TB drives into slots that held 10 TB drives.
• Mix 12 TB drives and 10 TB drives in the same storage column.
3.3.1.2 Removing a 3.5 inch drive
To remove a 3.5 inch drive:
1. If you are replacing a faulty drive, locate the drive and verify that is in the
Decommissioned
state.
Important:
The replacement drive must be the same model as the drive that you
are replacing. Also, the disk must be completely empty, with no data and no
partition table.
Important:
If you are removing drives as part of System or Storage Node
replacement, skip steps a through f.
a. On the
UniverStor SM Dashboard
,
click the
Resources
tab.
b. In the system image on the resources page, click the node with the faulty drive. The node will
have an alert icon, and the node status page will appear.
c. Scroll down the page to the components lists and click the tab for HDDs or SSDs depending on
which type of drive has failed.
d. Look through the list of drives and locate the faulty drive. The status column for the drive will
read
Degraded
,
Decommissioning
, or
Decommissioned
.
Note:
For more information about drive states, refer to the
UniverStor OS
Administrator Guide.
• If the status is
Degraded
, the drive has displayed problematic behavior and will undergo
automatic repair. If the problematic behavior continues, the drive will be decommissioned.
(DC01-SW02) #show startup-config
Required tools
Personnel required
Replacement time
None
1
15 to 25 minutes
Summary of Contents for ActiveScale P100
Page 103: ...ActiveScale P100 Support Guide 101...
Page 104: ...ActiveScale P100 Support Guide 102...
Page 120: ...ActiveScale P100 Support Guide 118...
Page 124: ...ActiveScale P100 Support Guide 122...
Page 131: ...ActiveScale P100 Support Guide 129...
Page 132: ...ActiveScale P100 Support Guide 130...