RMC-700 Enclosure –
Site accessible
1.
Launch an SSH session to the site device and run the
show discrete analog
command
to confirm device powering
a.
Correct power and wiring displays the following results:
RMC-700
ID State Resource State Value Mode Interval Description
0/power disable unassigned 26.4 V voltage 0
0/powerB enable assigned 26.2 V voltage 5 Battery inp
b.
Any other results mean the following:
i.
no value for 0/power and voltage displayed for 0/powerB indicates that the
RMC’s power was incorrectly wired
ii.
Voltage reading below 24 volts indicates that the power supply potentiometer
needs to be adjusted or that the power supply may be faulty
2.
If any of the non-correct results are displayed
a.
Create a ticket per the
b.
Create an
to dispatch an ATC FOT to the site to investigate further