background image

WESTELL .COM

CS19-URA-003

Universal Remote Annunicator
Installation and User Guide

This installation and user guide provides instructions to ensure correct and safe installation and interconnection of the Westell 
CS19-URA-003  Universal Remote Annunicator (URA).
Westell’s CS19-URA-003 URA can operate with any 

manufacturer’s public safety bi-directional amplifier (BDA) 
and battery backup system.  The URA connects to BDA relay 

outputs to provide visual and audible annunciation at 1 or 2 
locations up to 3000 feet away. 

The CS19-URA-003 includes:
• 

 a NEMA4 / UL 508A Interface Unit (IU) that mounts next to 

the BDA

• 

One or two Remote Annunciators

URA Installation Overview

Figure 1 below depicts a typical URA installation. 

• 

Level

• 

Screwdrivers

• 

Wire stripper

• 

Pliers

• 

Knife to cut flexible rubber conduit

Materials:

 

 

• 

Flexible rubber conduit

• 

CAT5 or CAT6 cable for Remote Annunciator connection(s)

• 

Standard wall-mounted 2-gang electrical junction box (1 for 
each Remote Annunciator)

Remote  

Annunciator

The URA Interface Unit is usually co-located with the Public 

Safety BBA and its BBU.  Multi-conductor cables connect the 
relays inside the URA Interface Unit to the BDA’s relay outputs 

and the Fire Alarm Control Panel. CAT5 or CAT6 Ethernet cable 
links the URA interface unit to one or two Remote Annunciators 
located up to 3000 feet away.

Installation Steps

1. 

Gather tools and materials.

Tools:

 

• 

Drill and drill bits

• 

Wrenches

BDA Closet

Fire Control Room

Lobby

URA  
Interface  
Unit

Westell eBDA or any
PS BDA with relay outputs

2nd Remote  

Annunciator

Fire Alarm Panel

Cat 5/6 cable
Multi-conductor cable

Figure 1. Overview of CS19-URA-003 Universal Remote Annunicator installation

2. 

Mount URA Interface Unit

The URA Interface Unit is wall-mounted using the brackets at 
top and bottom of the back of the unit. Follow these steps:

A. 

Determine the mounting location. Consider:

• 

proximity to the BDA and/or BBC cabinets

•   clearances needed to open cabinet(s) and install conduits

B. 

Lift the Interface Unit to the mounting location and 
mark each mounting hole. Use a level to ensure level 

mounting. Remove conduit fittings as needed to access 

lower mounting holes.

C. 

Drill  holes  at  each  mark  for  wall  anchors  fitting  #8  or 

Product 
label

Reviews: