WSS5O1O
Version 2.1
Installation
Manual
Page 1: ...WSS5O1O Version 2 1 Installation Manual...
Page 2: ...g Programming 20 4 5 1 LED Keypad 20 4 5 2 LCD Keypad 20 i Section 5 Program Description 5 1 Zone Definitions 21 5 2 Zone Attributes 23 5 3 Communicator Dialing 24 5 4 Communicator Phone Numbers 24 5...
Page 3: ...Preamble Telephone Number 44 Downloading Programming 401 First Downloading Option Code 45 402 Downloading Computer s Telephone Number 32 Digits 45 403 Downloading Access Code 45 404 Number of RIngs to...
Page 4: ...e WSS5204 module 1 WSS5204 Output Fully Supervised for Siren Output Powerful 1 Amp Regulated Power Supply 500 mA Auxiliary Supply 12 VDC Positive Temperature Coefficient PTC components replace fuses S...
Page 5: ...rum 900 MHz fully supervised and use standard AAA or AA alkaline batteries See Section 5 25 Wireless Expansion See WSS5132 RS Installation Manual Additional wireless devices are available WSSPIR WSSSM...
Page 6: ...door answer to the WSS5010 control panel The module also has talking and listening in capability for the central station See Section 5 28 Audio Interface Module Four additional devices are available W...
Page 7: ...Module Dimensions 165mm x 143mm x 38mm 6 5 x 5 625 x 1 5 approximately CMC 1 Attack Resistant Enclosure Listed enclosure for local installations where attack resistance is required Dimensions 288mm x...
Page 8: ...ders Step 5 Zone Wiring Section 2 9 Power down the control panel and complete all zone wiring Follow the guidelines provided in Section 2 9 to connect zones using normally closed loops single EOL resi...
Page 9: ...e equipment Connect the positive side of any alarm warning device to BELL the negative side to BELL The BELL output is protected if too much current is drawn from these terminals wiring short the BELL...
Page 10: ...hile YEL and GRN are clock and data The 4 Keybus terminals of the panel must be connected to the 4 Keybus terminals or wires of all modules The following conditions apply Keybus should be run in minim...
Page 11: ...A WSS5208 Output Module 50 mA WSS5923 EXT R Door Box Audio Station 35 mA WSS5132 RS Wireless Module 125 mA WSS5400 Serial Printer Module 62 mA Other Devices Read the manufacturer s literature carefull...
Page 12: ...de to enter Installer Programming Step 2 Press 000 for Keypad Programming Step 3 Press 0 for Slot Assignment Enter a two digit number to specify the system and slot assignment 1st digit Enter 1 2nd di...
Page 13: ...ot have enough power if the WSS5132 RS does not have any devices added 2 8 Removing Modules If a module is no longer required on the system the panel must be told to no longer supervise the module To...
Page 14: ...termine if the zone is in alarm tampered or faulted Wire the zones according to the following diagram ANY Z TERMINAL ANY COM TERMINAL ALARM CONTACT DOUBLE EOL CIRCUIT 1 NORMALLY CLOSED CONTACT WITH 56...
Page 15: ...the event to central station The zone programmed as LINKS Supervisory ALWAYS requires a single EOL resistor 5 6K and must be wired according to the following diagram 2 9 7 LINKS Answer Shall not be us...
Page 16: ...de can perform the same basic system functions as the System Master Code In addition it can be used to program the 32 User Codes and 2 Duress Codes on the system Duress Codes By default Duress Codes a...
Page 17: ...user codes with the Bypass attribute enabled will be able to bypass zones See Section 3 4 Commands 5 Zones can only be bypassed when the system is disarmed To bypass a zone 1 Enter 1 Access Code 2 Th...
Page 18: ...dule has a low backup battery Light 8 WSS5204 AC Failure The WSS5204 module has lost AC power Trouble 2 AC Failure This trouble indicates that AC power is no longer being supplied to the control unit...
Page 19: ...tes determine what abilities the code will have The programmable attributes are as follows Pager Communications Zone Bypassing Day Zone Reset Phone Access on WSS5580 User Codes Access Codes 01 to 32 E...
Page 20: ...the number 1 to 7 for the item to be programmed 1 Time and Date The time and date must be accurate for the Test Transmission function to work properly In addition the event buffer time and date stamp...
Page 21: ...Section 5 1 Zone Definitions 9 must be entered after the Stay or Away function key has been pressed Master Code Not Changeable option Section 015 Option 4 Quick Exit Enable Section 015 Option 2 3 5 Fu...
Page 22: ...2 Programming Decimal Data When the Ready light is ON the panel is waiting for the information to be programmed for the selected Section Enter the information written in the boxes for the Section fou...
Page 23: ...ough the keypad When a Section is entered the keypad will immediately display the first digit of information programmed in that Section The keypad displays the information using a binary format where...
Page 24: ...ch as motion detectors 05 Interior Stay Away Zone This zone type works the same as the Interior zone type with one exception The zone will be automatically bypassed when the panel is armed with the St...
Page 25: ...Hour Burglary Zone If this zone is violated whether armed or disarmed the panel will immediately latch the alarm output and communicate to the central station The alarm will sound for the Bell Cutoff...
Page 26: ...ne Cross Zoning Enable Cross Zoning is used for alarm verification and false alarm reduction Zones are enabled as cross zones using the Cross Zone attribute If a valid time is programmed in the Cross...
Page 27: ...mmunicator Phone Numbers The panel can call 2 different phone numbers for communication purposes The 1st Phone Number is used to call central station using SIA format the 2nd Phone Number is used to c...
Page 28: ...the central station All other zone types will only go into alarm if the panel is armed 5 7 2 Zone Restoral If the Restoral on Bell Timeout option is selected the panel will send the Zone Restoral Repo...
Page 29: ...the AC Failure Communication Delay The AC Failure Trouble Restoral Reporting Code will be transmitted as soon as AC power is restored A Bell Circuit Trouble Alarm Reporting Code will be transmitted im...
Page 30: ...a report will be transmitted to the programmed telephone number Once the exception report has been transmitted no more report will be sent until an interior movement detected and the timer once again...
Page 31: ...9 1 PGM Output Options 01 Burglary and Fire Bell Output The PGM output will activate when the alarm output is active and will turn off when the alarm output is silenced If the alarm output is pulsing...
Page 32: ...ng software package 16 LINKS 1000 Support PGM1 Only The PGM output will be used as a data wire to communicate phone number information for the LINKS 1000 cellular unit 17 Fire Bell Follower The PGM ou...
Page 33: ...ll wait the TLM Trouble Delay time before indicating the trouble so that a momentary interruption of the phone line will not cause a trouble condition The TLM Trouble Only or Audible When Armed option...
Page 34: ...r of the previous alarm Since two Delay zones are programmable and therefore two different Entry Delays when the panel is armed it will use the Entry Delay for the first Delay zone violated If Exit De...
Page 35: ...ccessful and Default Failed Sensor Reset XX Critical Shutdown 6 Access XX Swinger Shutdown Keypad Lockout Event Buffer Follows Swinger Shutdown Section 013 Option 7 5 16 Swinger Shutdown The swinger s...
Page 36: ...has been reached the panel will lock out the keypad for the Lockout Duration and log the event to the event buffer For the duration of the lockout the panel will sound an error tone when any key is pr...
Page 37: ...n the device will also indicate the status of the battery If a low battery condition exists the panel will indicate a General Transmitter Low Battery trouble The panel will delay reporting the event f...
Page 38: ...central station monitoring The central station can select the audio station listen talk extend on line time and hang up Each station home runs to the Audio Interface module using standard 22 gauge 4...
Page 39: ...toring station to notify once walk test has started Violating a fire zone in walk test will transmit a zone tamper One walk test must be ended before another walk test can be started 5 31 1 Buzzer Wal...
Page 40: ...I WSS5208 Output Expander I _ _____________________________________________________________________________________ _ _ _ _ _ _ _ _ _ _ I WSS5400 Serial Printer Module I _ ___________________________...
Page 41: ...5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Zone 25 Zone 26 Zone 27 Zone 28 Zone 29 Zone 30 Z...
Page 42: ...NKS Answer 07 Delayed 24 Hour Fire Hardwired 16 24 Hour Medical 87 Delayed 24 Hour Fire Wireless 08 Standard 24 Hour Fire Hardwired 17 24 Hour Panic 88 Standard 24 Hour Fire Wireless Shall not be used...
Page 43: ...ary and Fire Bell Output 16 LINKS 1000 Support PGM 1 only 02 Utility Output 17 Fire Bell 03 Sensor Reset 18 Burglary Bell 04 2 Wire Smoke Support PGM2 ONLY 19 Latched Strobe 05 System Armed Status 20...
Page 44: ...______I 2 2 2 2 2 Bell Squawk on Trouble No Bell Squawk on Trouble 3 4 ON I__ ______I 3 3 3 3 3 Audible Exit Beeps with Urgency Silent Exit Delay 5 14 OFF I__ ______I 4 4 4 4 4 Exit Delay Termination...
Page 45: ...__ I________ I________ I________I 103 Zone 3 I________I I________ I________ I________ I________ I________ I________ I________I 104 Zone 4 I________I I________ I________ I________ I________ I________ I...
Page 46: ...ection 5 7 Communicator Reporting Codes Default 000 I_ ______I_ ______I _ ______I Valid entries are 001 255 hours 172 WSSFOB PGM Pulse Timer Section 5 9 PGM Outputs Default 005 I_ ______I_ ______I _ _...
Page 47: ..._I _ ______I Swinger Shutdown Maint and Rest 001 014 Transmissions 000 disabled 5 16 000 I_ ______I_ ______I _ ______I Communication Delay 001 255 seconds 5 17 060 I_ ______I_ ______I _ ______I AC Fai...
Page 48: ..._ ____I_ ____I_ ____I_ ____I_ ____I_____I_ ____I_ ____I_ ____I_ ____I_ ____I_____I_ ____I_ ____I_ ____I_ ____I 403 Downloading Access Code Section 5 8 Downloading Enter 6 Hexidecimal digits I__ _____I...
Page 49: ..._ _____I__ _____I__ _____I__ _____I 20 20 20 20 20 Zone 20 I__ _____I__ _____I__ _____I__ _____I__ _____I 05 05 05 05 05 Zone 5 I_______I__ _____I__ _____I__ _____I__ _____I 21 21 21 21 21 Zone 21 I__...
Page 50: ...9 No Entry Arm 17 1 Reactivate Stay Aways 27 Disarm OFF 06 Chime ON OFF 18 For Future Use Key fob only Handheld Keypad Options Default 00000 57 Function Key 1 l____l____l 59 Function Key 3 l____l____...
Page 51: ...Option 2 Zone 18 Supervision enabled Disabled l________l Option 3 Zone 19 Supervision enabled Disabled l________l Option 4 Zone 20 Supervision enabled Disabled l________l Option 5 Zone 21 Supervision...
Page 52: ...P R O G R A M M I N G W O R K S H E E T S How to Program the WSS5500 Keypad If you have an WSS5500 Keypad additional programming is required for proper operation The following is a description of the...
Page 53: ...I_ ____I_____I 22 Zone 22 Label Zone____22____ I_____I_____I_____I_ ____I__ ___I_ ____I_ ____I_ ____I_ ____I_ ____I_ ____I_ ____I_ ____I_____I 23 Zone 23 Label Zone____23____ I_____I_____I_____I_ ____...
Page 54: ..._____I 3 3 3 3 3 P Keys enabled Panic Keys disabled OFF I__ _____I 4 8 4 8 4 8 4 8 4 8 For Future Use 66 Keypad Options Default Option ON OFF ON I__ _____I 1 1 1 1 1 Display Access Code when Programm...
Page 55: ...H 00 Keypad Auxiliary Alarm Restore MA 00 MH 00 Keypad Panic Alarm Restore PA 00 PH 00 2 Wire Smoke Alarm Restore FA 99 FH 99 Zone Tamper 1 32 TA XX Zone Tamper Restorals 1 32 TR XX General System Tam...
Page 56: ...er 19 69 Opening By User 20 70 Opening By User 21 71 Opening By User 22 72 Opening By User 23 73 Opening By User 24 74 Opening By User 25 75 Opening By User 26 76 Opening By User 27 77 Opening By User...
Page 57: ...Hookup Diagram W S S 5 0 1 0 C O N T R O L P A N E L 54...
Page 58: ......
Page 59: ...rminal equipment Standard jacks shall be so arranged that if the plug connected thereto is withdrawn no interference to the operation of the equipment at the customer s premises which remains connecte...
Page 60: ...Westar Security Services 1 800 654 6770 Printed in North America 29002434 R1...