Installation and Connection
50 | CTW900
Configuration 2 – Run/Stop function with two-wire control (Remote Mode)
Valid for factory default setting and converter operating in the remote mode.
In the factory default, the selection of the operating mode (local/ remote) is done by the key
, and the selected
mode at power-up is Local.
In order to define the selected mode after the power-up as Remote, you must set P0220 = 3.
Figure 5.14
– Connections in XC1 for configuration 2
Configuration 3 – Run/Stop function with three-wire control
Enabling of the Run/Stop function with three-wire control.
Parameters to be set:
■
P0264 = 8 (DI2 for Direction of Rotation);
■
P0265 = 6 (DI3 for Start);
■
P0266 = 7 (DI4 for Stop);
■
P0223 = 4 and P0224 = 1 (DIx), in case the three-wire control in Local mode is desired or;
■
P0226 = 4 and P0227 = 1 (DIx), in case the three-wire control in Remote mode is desired.
S1 and S2 are pulsing push-buttons for ‘Turn ON’ (NO contact) and ‘Turn OFF’ (NC contact), respectively.