Quick Parameter Reference
.
14 | CTW900
Param.
Function
Adjustable Range
Factory
Setting
User’s
Setting
Proper.
Groups
Page
P0249
AI4 Offset
-100.00 to 100.00 %
0.00 %
32
85
P0250
AI4 Filter
0.00 to 16.00 s
0.01 s
32
85
P0251
AO1 Function
0 = Speed Ref.
3
33
87
1 = Ref. After Ramp
2 = Total Ref.
3 = Real Speed
4 = Speed Error
5 = Speed Reg. Output
6 = Current Ref.
7 = Armature Curr.
8 = Curr. Reg. Output
9 = Firing Angle
10 = Output Power
11 = Motor Torque
12 = SoftPLC
13 = Not Used
14 = Armature Voltage
15 = Encoder Speed
16 = Field current
17 = EMF
18 = P0696 Value
19 = P0697 Value
20 = P0698 Value
21 = P0699 Value
P0252
AO1 Gain
0.000 to 9.999
1.000
33
88
P0253
AO1 Signal Type
0 = 0 to 10 V/ 20 mA
0
CFG1
33
89
1 = 4 to 20 mA
2 = 10 V/ 20 mA to 0
3 = 20 to 4 mA
P0254
AO2 Function
See options in P0251
7
33
87
P0255
AO2 Gain
0.000 to 9.999
1.000
33
88
P0256
AO2 Signal Type
0 = 0 to 10 V/ 20 mA
0
CFG1
33
89
1 = 4 to 20 mA
2 = 10 V/ 20 mA to 0
3 = 20 to 4 mA
P0257
AO3 Function
See options in P0251
2
33
87
P0258
AO3 Gain
0.000 to 9.999
1.000
33
88
P0259
AO3 Signal Type
0 = 0 to 20 mA
4
CFG1
33
89
1 = 4 to 20 mA
2 = 20 to 0 mA
3 = 20 to 4 mA
4 = 0 to 10 V
5 = 10 to 0 V
6 = -10 to +10 V
P0260
AO4 Function
See options in P0251
5
33
87
P0261
AO4 Gain
0.000 to 9.999
1.000
33
88
P0262
AO4 Signal Type
0 = 0 to 20 mA
4
CFG1
33
89
1 = 4 to 20 mA
2 = 20 to 0 mA
3 = 20 to 4 mA
4 = 0 to 10 V
5 = 10 to 0 V
6 = -10 to +10 V