23
• The sensors should detect the material only, and not the means of conveyance (e.g. pallet).
Muting Sensor
Muting Sensor
Material
Pallet
Conveyor Level
The sensors should detect the load,
and not the pallet.
• The material must be detected throughout the entire muting zone, i.e. the sensors’ output signals must remain
unchanged. This requirement must above all be adhered to when the material is uneven, is shifted when it enters
the muting zone or if its height changes.
6.2 Connecting the Muting Sensors and the Muting Indicator
6.2.1 Muting Sensors
The muting sensors must be integrated into the system as shown in the following diagram.
Muting
Transmitter 1
Muting
Transmitter 2
Muting
Receiver 1
Muting
Receiver 2
6.2.2 Muting Indicator
The muting indicator must be integrated into the system as shown in the following diagram.
Muting Indicator
Muting
Signal
Monitor
24 V DC
0 V
0 V