Parameters Configuration
150
9.5 Parametrization via the IO-Link Interface
9.5.1 Requirements and Framework Conditions
The following requirements must be met to parametrize the ESPE via IO-Link:
• The system connection of the ESPE is connected to the IO-Link master via the T-plug (ZC7G001).
• The IO-Link master is equipped with the latest software version.
• The current IODD (device description file) for the ESPE used is present and available in the master.
• Master and ESPE are connected with each other (online).
NOTE!
The latest versions of the software, IODD and the interface protocol are available on the
wenglor homepage in the download area for the product.
If the connection is successful, the following operating displays are shown during the parameter configuration
via IO-Link (see
and
:
Emitter
Display
External parametrization
1
POWER
LED lit
2
CODE
LED off
3
HI RAN
LED off
4
ERROR
LED blinks
Receiver
Display
External parametrization
1
OSSD 1 (LED 1, red)
LED lit
OSSD 2 (LED 2, green)
LED off
2
RES
LED off
3
SIG LOW
LED off
4
ERROR
LED flashes
Segment display:
Digit 1
Digit 2
Digit 3
Digit 4
NOTE!
The parameter configuration on the control panel (see
Section 9.3, page 117, Section 9.4,
always has priority over setting via IO-Link.