Part Number: 9294045 07/17
7
Section 2
Installation
Electrical Service
DANGER
Check all wiring connections, including factory
terminals, before operation. Connections can become
loose during shipment and installation.
DANGER
Units with two power cords must be plugged into
individual branch circuits. During movement, cleaning
or repair it is necessary to unplug both power cords.
n
Warning
This appliance must be grounded and all field wiring
must conform to all applicable local and national
codes. Refer to rating plate for proper voltage. It is the
responsibility of the end user to provide the disconnect
means to satisfy the authority having jurisdiction.
VOLTAGE
All electrical work, including wire routing and grounding,
must conform to local, state and national electrical codes.
The following precautions must be observed:
• The equipment must be grounded.
• A separate fuse/circuit breaker must be provided for
each unit.
• The maximum allowable voltage variation is ±10% of
the rated voltage at equipment start-up (when the
electrical load is highest).
• Check all green ground screws, cables and wire
connections to verify they are tight before start-up.
GROUND FAULT CIRCUIT INTERRUPTER
Ground Fault Circuit Interrupter (GFCI/GFI) protection is
a system that shuts down the electric circuit (opens it)
when it senses an unexpected loss of power, presumably
to ground. Welbilt does not recommend the use of GFCI/
GFI circuit protection to energize our equipment. If code
requires the use of a GFCI/GFI then you must follow the
local code. The circuit must be dedicated, sized properly
and there must be a panel GFCI/GFI breaker. We do not
recommend the use of GFCI/GFI outlets to energize our
equipment as they are known for more intermittent
nuisance trips than panel breakers.
RATED AMPERAGES, HORSEPOWER, VOLTAGE &
POWER CORD CHART
Units with plugs are supplied with approximately 6ft
(183cm) cords.
Models 406 and 407 may be stacked using a stacking collar.
In this case two 6ft (183cm) long grounded supply cords
and plugs are standard.
Model
Amps
HP
Voltage,
Cycle, Phase
NEMA
Plug
402P
4.0
1/5
115/60/1
5-15P
406P
4.0
406CAP
4.0
407
5.8
407CA
5.8
ST4048P
4.0
UC4048P
4.0
1/5
Refrigeration
Model
BTU/Hour
Capacity
Heat of
Rejection
Refg Charge
402P
1356
210
100g R290
406P
1356
210
100g R290
406CAP
1356
210
100g R290
407
800
339
6.5oz R404A
407CA
800
339
6.5oz R404A
ST4048P
1356
316
100g R290
UC4048P
1356
316
100g R290
Drain Connections
n
Warning
If a refrigerated base does not have a condensate
evaporator supplied, you must connect the condensate
line to a suitable drain. Otherwise, water will collect on
the floor, causing a potentially hazardous situation.
n
Warning
Moisture collecting from improper drainage can create a
slippery surface on the floor and a hazard to employees.
It is the owner’s responsibility to provide a container or
outlet for drainage.