9.6 Electrical supply, Korea
C4 EB/ES (single-phase FC)
12.20
20.10
20.20
3~ 220 V 60 Hz (3/PE)
Rated power consumption
[kW]
30.6
35.3
61.1
Convection power
[kW]
30.2
34.6
60.4
Steam power (EB only)
[kW]
28.6
28.6
36.5
Motor power
[kW]
0.35
0.7
0.7
Rated current
[A]
80.3
92.6
160.3
Fuse rating
[A]
100
100
160
Residual current
[mA]
-
-
-
Protective earth current
[mA]
-
-
-
Recommended conductor cross-section for wires laid uncovered in air up
to 5 m in length.
[mm
2
]
4G35
4G35
4G70
Residual-current device
Type
A/B
A/B
A/B
3N~ 380V 60Hz (3/N/PE)
Rated power consumption
[kW]
30.5
35.1
60.7
Convection power
[kW]
30.1
34.4
60.0
Steam power (EB only)
[kW]
28.5
28.5
36.3
Motor power
[kW]
0.35
0.7
0.7
Rated current
[A]
46.3
53.3
92.2
Fuse rating
[A]
50
63
100
Residual current
[mA]
~7.5
~16.5
~16.5
Protective earth current
[mA]
~7.5
~16.5
~16.5
Recommended conductor cross-section for wires laid uncovered in air up
to 5 m in length.
[mm
2
]
5G16
5G16
5G35
Residual-current device
Type
A/B
A/B
A/B
9 Technical data
Installation manual
81