5.6 Electrical installation
DANGER
Electric shock when working with voltage applied
The consequence is serious injury or death.
▶
Isolate unit prior to carrying out work and protect against accidental reconnection
to the mains.
The electrical installation must only be carried out by qualified electricians, local reg-
ulations must be observed.
Install Bus and external sensor cable separately and preferably using screened cables
(metal braiding).
Separate ducts are provided for the separate installation of 230 V cables opposite to
Bus and sensor cables (SELV).
▶
Feed the cables from the rear of the unit through the cable ducts to the connection
box.
▶
Assign the inputs and outputs according to application (see Ch. 6.10).
▶
Fit screen of Bus and external sensor cable to the designated screen connection
terminals.
▶
Connect the cables according to the wiring diagram, in the process pay particular
attention to the correct phase location of the voltage supply.