5.1.2 Fill water quantity
If information about the fill water quantity is not available, the following table can be
used to estimate the quantity.
Heating system
Estimated fill water quantity
(1
55/45 °C
70/55 °C
Pipe and steel radiators
37 l/kW
23 l/kW
Cast iron radiators
28 l/kW
18 l/kW
Panel radiators
15 l/kW
10 l/kW
Air conditioning
12 l/kW
8 l/kW
Convectors
10 l/kW
6 l/kW
Underfloor heating
25 l/kW
25 l/kW
(1
based on the heating requirements of the building.