Installation and operating instruction
Gas condensing unit WTC-GB 15-B Compact and WTC-GB 25-B Compact
9 Servicing
83309302 1/2018-05 La
121-196
Prior to every servicing
Inform the operator about the extent of service work to be carried out.
Carry out input measurement [ch. 6.6.7.2].
Switch off mains switch of installation and safeguard against accidental reactiva-
tion.
Close fuel shut off devices.
Remove front panel of fresh water storage tank.
Remove front panel of condensing unit.
Service
Carry out servicing in accordance with the enclosed inspection card (Print No.
837569xx).
Following servicing
DANGER
Risk of electric shock
Touching the ignition device can lead to electric shock.
Do not touch ignition device during the ignition process.
Check soundness of gas valve train [ch. 7.1.1]
Check soundness of flue gas and condensate carrying components.
Check tightness of water carrying components.
Check soundness of burner cover / fan connection and burner cover / heat ex-
changer connection.
Mount the front panel of condensing unit and secure the tension lock with the
screw.
Fit front panel of fresh water storage tank.
Carry out flue gas measurement (calibration, O
2
correction), see [ch. 6.6.7.3].
Enter combustion values and settings in the commissioning record.
Resetting the service display [ch. 6.6.7].
9.1.2 Components
In addition to the servicing steps listed in the inspection card, the following com-
ponents must be tested for their design lifespan.
Components, which show increased wear and tear or whose design lifespan is or
will be exceeded prior to the next service should be replaced as a precaution.
Check the design lifespan of the components.
Replace components as necessary
Components
Design lifespan
WEM-FA-G device electronics
10 years or 360 000 burner starts
Gas combi valve
10 years or 500 000 burner starts
Gasket fan air outlet
10 years
Seal gas valve / fan
10 years
Burner gasket
10 years
Safety valve 3 bar
10 years