3 Operation
17-36
Special
level
Defines the flow temperature set at special level. The
heating program is not effective.
When input H1 is closed, the system heats up to the
special flow level set.
Only if input H1 is configured to
Heating cir-
cuit 1: Special level
.
Holiday
Interrupt heating program for a certain period of time. The
level can be set to
Setback
or
Frost
during this
time.
Set
Function
to
On
.
Set
Room setpoint temperature
to
Setback
or
Frost
.
Enter
Start date
and
End date
.
If the parameter is set to
Off
, the current heating pro-
gram is activated.
Heating curve
Flow setpoint temperature dependent on external
.
The display refers to the room setpoint temperature
Normal
.
The heating curve gradient can be changed and / or it
can be moved in parallel.
Gradient
(1
Parallel movement
(1
Adapting the heating
cold external temperature: change gradient
mild external temperature: change parallel movement
Only with control variation
Weather dependent
control
or
Weather/Room control
.
Su/Wi
change-over
Configure Summer-Winter change-over.
On
(factory setting):
If the damped external temperature (tendentious course)
exceeds the
Change-over temperature
(factory
setting:
19 °C
), the
Operating mode
changes to
Summer
.
Off
:
The operating mode set remains activated, independent
of the external temperature.
(1
Factory setting and setting range depending on heating circuit
set, see installation and operating manual for condensing unit.