Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
83252902 1/2019-09 La
20-84
4.2 Check rating
The burner as delivered has been:
pre-sized for a specific oil throughput,
equipped with an oil nozzle type -w- K3 S1 50°.
The exact details are documented on the burner data sheet.
Pump pressure setting
30 bar
Determine exact oil throughput at oil meter or by weighing.
Nozzle selection table -w- K3 S1 50°
The following minimum capacity values are achieved with an oil quantity regulator
setting of 90°.
Burner capacity [kW] at pump pressure
Nozzle size [kg/h]
20 bar
22 bar
24 bar
26 bar
28 bar
30 bar
90
851
893
934
976
1017
1059
100
898
941
984
1027
1070
1113
110
987
1035
1083
1130
1178
1226
120
1095
1147
1200
1252
2305
1357
130
1214
1272
1330
1389
1447
1505
140
1297
1359
1421
1483
1545
1607
150
1416
1483
1549
1616
1682
1749
160
1505
1576
1648
1719
1791
1862
170
1624
1700
1776
1853
1929
2005
180
1708
1788
1867
1947
2026
2106