Installation and operating instruction
Oil burner WL5/2-B
7 Commissioning
83272202 1/2019-04 La
29-76
Set diffuser
With dimension X = 0mm the indicating bolt is flush with the nozzle assembly
cover.
Turn screw
1
, until dimension X equals the value determined.
X
1
Set air damper
Turn setting screw
1
until the scale shows the value determined.
A
B
1
1
A Manual adjustment
B Actuator (optional)
Determine mixing pressure
Determine the mixing pressure required for the preset combustion heat rating
from the diagram and note down.
2
1
24
28
32
36
40
44
48
52
56
2.6
2.7
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
1
Combustion heat rating [kW]
2
Mixing pressure [mbar]
Guide values, which may vary depending on combustion chamber resist-
ance.