Installation and operating instruction
Oil burner WL5/1-B H

12 Project planning

83272102 1/2019-03 La

58-76

12 Project planning

12.1 Oil supply

Observe EN 12514-2, DIN 4755, TRÖI and local regulations.

General information relating to the oil supply

Do not use cathode protection system with steel tanks.
With oil temperatures < 5 °C, the separation of paraffin can cause oil lines, oil fil-
ters and nozzles to become blocked. Avoid placing oil tanks and pipelines in
areas subject to frost.
The oil supply should be installed in such a way that the oil hoses can be con-
nected free of tension.
Fit oil filter in front of pump, recommended mesh aperture 70 μm.

Suction resistance and supply pressure

CAUTION

Pump damage due to excessive suction resistance

A suction resistance greater than 0.4 bar can damage the pump.

Reduce suction resistance – or – install oil supply pump or suction unit, whilst
observing the maximum supply pressure at the oil filter.

The suction resistance depends on:

suction line length and diameter,
pressure loss of oil filter and other components,
lowest oil level in the oil storage tank (max 3.5 m below the oil pump).

If an oil feeder pump is installed:

max 1.5 bar supply pressure at oil filter,
max 0.7 bar supply pressure into automatic de-aerator.

Elevated oil level

If the suction line is leaking the tank can be siphoned dry. An electric anti siphon
valve 

1

 can prevent this.

Observe manufacturers instructions regarding pressure loss caused by anti si-
phon valve.
The anti siphon valve must close with a delay and show a pressure relief towards
the oil storage tank.

Maintain height differences:

max 4.6 m between oil level and anti siphon valve,
on single pipe system max 8 m between anti siphon valve and automatic de-aer-
ator,
on two pipe system max 20 m between anti siphon valve and oil pump.

 max 8 m

 max 4.6 m

 max 20 m

 max 4.6 m

1

1

Summary of Contents for WL5/1-B H

Page 1: ...Installation and operating instruction Oil burner WL5 1 B H 83272102 1 2019 03 ...

Page 2: ...1 Air supply 10 3 3 2 Oil supply 10 3 3 3 Electrical components 11 3 3 4 Program sequence 12 3 4 Technical data 14 3 4 1 Approval data 14 3 4 2 Electrical data 14 3 4 3 Ambient conditions 14 3 4 4 Fuels 14 3 4 5 Emissions 15 3 4 6 Rating 16 3 4 7 Dimensions 17 3 4 8 Weight 17 4 Installation 18 4 1 Installation conditions 18 4 2 Selecting a nozzle 19 4 3 Burner installation 20 4 3 1 Rotate burner b...

Page 3: ... 9 9 Set mixing head 43 9 10 Removing the air regulator 44 9 11 Removing and refitting oil pump 45 9 12 Removing and refitting fan wheel 46 9 13 Remove burner motor 47 9 14 Removing and refitting oil pump filter 48 9 15 Replacing the fuse 49 10 Troubleshooting 50 10 1 Procedures for fault conditions 50 10 1 1 Illuminated push button off 50 10 1 2 Illuminated push button red 51 10 1 3 Illuminated p...

Page 4: ...carried out by personnel who have the relevant train ing and instruction Persons with limited physical sensory or mental capabilities may only work on the unit if they are supervised or have been trained by an authorised person Children must not play with the unit 1 2 Symbols DANGER Immediate danger with high risk Non observance can lead to serious injury or death WARNING Danger with medium risk N...

Page 5: ...servance of the manual operation with faulty safety equipment continual operation despite a fault improper installation commissioning operation and service repairs which have been carried out incorrectly the use of non original Weishaupt parts force majeure unauthorised modifications made to the unit the installation of additional components which have not been tested with the unit the installatio...

Page 6: ...2 2 Safety measures Safety relevant fault conditions must be eliminated immediately Components which show increased wear and tear or whose design lifespan is or will be exceeded prior to the next service should be replaced as a precaution The design lifespan of the components is listed in the service plan ch 9 2 2 2 1 Normal operation All labels on the unit must be kept in a legible condition Stip...

Page 7: ...all components fitted to the combustion system Prolonged exposure to high noise levels can lead to loss of hearing Provide oper ating personnel with protective equipment Noise emissions can further be reduced with a sound attenuator 2 5 Disposal Dispose of all materials and components in a safe and environmentally friendly way at an authorised location Observe local regulations ...

Page 8: ...uction Oil burner WL5 1 B H 3 Product description 83272102 1 2019 03 La 8 76 3 Product description 3 1 Type key WL5 1 B H W Type W burner L Fuel Oil EL 5 Size 1 Ratings size B Construction H Version Nozzle assembly with oil preheating ...

Page 9: ...ction Oil burner WL5 1 B H 3 Product description 83272102 1 2019 03 La 9 76 3 2 Serial number The serial number on the name plate identifies the product This is required by Weishaupt s customer service department 1 1 Name plate Ser No ...

Page 10: ...g the diffuser This adjusts the mixing pressure and the air quantity required for combustion 3 3 2 Oil supply Oil pump The pump draws the oil through the supply line and carries it under pressure to the oil nozzle The pressure regulating valve keeps the oil pressure constant A solenoid valve opens and closes the oil supply to the nozzle The pressure regu lating valve and solenoid valve are integra...

Page 11: ...r It controls the sequence of operation and monitors the flame Burner motor The burner motor drives the fan wheel and the oil pump Ignition unit The electronic ignition unit creates a spark at the electrode which ignites the fuel air mixture Flame sensor The combustion manager monitors the flame signal via the flame sensor If the flame signal becomes too weak the combustion manager carries out a c...

Page 12: ...to Open position If the actuator limit switch S2 is closed the burner motor starts The combustion chamber is pre purged Ignition Ignition starts with the pre purge time TV Fuel release Following the pre purge time TV the solenoid valve K11 opens and releases the fuel Safety time With fuel release safety time TS and post ignition time TNZ start The flame signal must be present within the safety tim...

Page 13: ...ation time 1 s E1 Heat exchanger TN Post purge time 1 2 s F2 Temperature or pressure limiter TNZ Post purge time 6 5 s K10 Anti siphon valve optional TS Safety time 4 6 s K11 Solenoid valve TV Pre purge time 16 2 s M1 Burner motor Voltage is applied M20 Air damper actuator optional Flame signal present P11 Control lamp operation optional Current path S2 Actuator limit switch optional START orange ...

Page 14: ...Consumption at start max 239 W Consumption during operation max 139 W Power consumption max 1 0 A Internal unit fuse T6 3H IEC 127 2 5 External fuse max 16 AB 3 4 3 Ambient conditions Temperature in operation 10 1 40 C Temperature during transport storage 20 70 C relative humidity max 80 no dew point 1 with the relevant suitable fuel oil and layout of oil supply 3 4 4 Fuels Fuel oil EL to DIN 5160...

Page 15: ...uel combustion air temperature and humidity medium temperature Sound levels Dual number noise emission values Measured sound power level LWA re 1 pW Uncertainty value KWA 62 4 dB A 1 dB A Measured sound pressure level LpA re 20 μPa Uncertainty value KpA 55 4 dB A 2 dB A 1 Determined to ISO 9614 2 2 Determined at 1 metre distance from the front of the burner The measured noise levels plus uncertain...

Page 16: ...r fuel oil EL Capacity graph Capacity graph to EN 267 The capacity data given relates to an installation elevation of 500 m above sea level For installation elevations above 500 m a capacity reduction of approx 1 per 100 m applies A limited capacity graph is valid for ducted air intake 0 0 1 0 2 0 3 0 4 0 5 0 6 0 1 0 2 0 3 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 1 2 1 6 1 4 1 8 2 0 2 2 2 4 2 ...

Page 17: ...ating instruction Oil burner WL5 1 B H 3 Product description 83272102 1 2019 03 La 17 76 3 4 7 Dimensions Burner 308 mm 135 mm 143 mm 30 mm 286 mm 292 mm 90 mm 154 mm weishaupt 292 mm 31 mm 216 mm 3 4 8 Weight approx 11 kg ...

Page 18: ...icient combustion air is available if necessary install ducted air intake Prepare heat exchanger The refractory 3 must not protrude beyond the front edge of the combustion head The refractory can take a conical shape min 60 Refractory may not be required on boilers with water cooled front unless the man ufacturer gives other instructions Following installation the aperture 4 between flame tube and...

Page 19: ...ngle varies depending on pump pressure Nozzle selection table Different load values are possible due to tolerances Burner capacity kW at pump pressure Nozzle size gph 10 bar 11 bar 12 bar 13 bar 14 bar 0 40 16 7 17 4 18 1 18 8 0 45 17 9 18 7 19 6 20 3 21 2 0 50 20 0 20 8 21 7 22 7 23 7 0 55 21 9 22 9 23 9 25 0 25 9 0 60 23 9 25 1 26 1 27 2 28 2 0 65 25 9 27 2 28 3 29 4 30 8 0 75 30 0 31 3 32 6 34 ...

Page 20: ...changer using screws 3 The aperture between combustion head and refractory should be filled with flame proof resilient insulating material do not make solid 1 3 2 It is possible to install the burner rotated by 180 if space is limited This requires conversion measures ch 4 3 1 Fit nozzle ch 9 4 Set ignition electrodes ch 9 6 Check nozzle distance and adjust if necessary ch 9 9 Mount burner with sc...

Page 21: ...position A ch 9 3 Undo screw 1 on diffuser and turn diffuser by 180 Fit nozzle Set ignition electrodes ch 9 6 Check nozzle distance and adjust if necessary ch 9 9 Rotate burner by 180 and secure with screws 3 Remove oil line 4 Remove pressure hose 5 from nozzle assembly Undo fixing screws 2 for oil pump and rotate oil pump by 180 Tighten screws 2 Connect pressure hose 5 Fit pressure hose 6 supplie...

Page 22: ... max 2 bar 1 Supply temperature max 60 C 1 1 Measured at the pump Check conditions for oil hoses Length 1200 mm Oil hose connection G Nominal pressure 10 bar Thermal load max 100 C Connect oil supply CAUTION Damage to the oil pump caused by incorrect connection Mixing up supply and return can damage the oil pump Ensure correct connection of oil hoses to the supply and return of the pump Fit oil ho...

Page 23: ... tension consider length of hose required for the service position do not kink oil hoses curve radius 1 of 50 mm must be maintained If these conditions for connection can not be met Adapt oil supply on site 1 Purge oil supply and ensure it is tight CAUTION Oil pump seized due to running dry Pump could be damaged Fill oil supply with oil and purge Ensure oil supply is tight ...

Page 24: ...shock Isolate the device from the power supply prior to starting any work Safeguard against accidental restart The electrical connection must only be carried out by qualified electricians Ob serve local regulations Observe wiring diagram ch 11 2 Check polarity and wiring of 7 pole connection plug 1 Plug in connection plug 1 1 With remote reset install connection line separately Do not exceed maxim...

Page 25: ...ss illuminated push button The illuminated push button on the combustion manager has the following func tions display operating condition ch 6 2 display fault codes ch 10 1 2 reset burner lockout ch 10 1 2 Re starting the burner during burner operation Press illuminated push button for 1 second 6 2 Display Illuminated push button Operating condition orange Start phase Flashing orange Ignition and ...

Page 26: ...filled the heat exchanger is filled with medium the regulating control and safety devices are functioning and set correctly the flue gas ducts are unimpeded a measuring point conforming to standards is available to measure the flue gas the heat exchanger and flue gas ducting up to the test point are sound ex traneous air influences the test results the operating instructions of the heat exchanger ...

Page 27: ...B4 Extraneous light detection from 13 μA 16 μA Minimum flame signal 35 μA 35 μA Recommended flame signal 70 120 μA 45 72 μA 1 2 Oil pressure measuring devices on oil pump Vacuum gauge for suction resistance supply pressure Pressure gauge for pump pressure WARNING Oil leakage from oil pressure measuring devices due to constant load Oil pressure measuring devices could be damaged and cause environme...

Page 28: ...ner outside of the capacity graph Determine the diffuser setting dimension X and air damper setting required from the diagram and note down Example Burner capacity required 33 kW Diffuser setting dimension X 7 6 mm Air damper setting 6 3 Diffuser default settings 2 1 4 5 6 7 8 9 10 18 16 14 20 22 24 26 28 30 32 34 36 38 40 42 3 2 1 Combustion heat rating kW 2 Diffuser settings dimension X mm Air d...

Page 29: ... 29 76 Set diffuser With dimension X 0 mm the indicating bolt is flush with the cover of the nozzle assembly Turn screw 1 until dimension X equals the value determined X 1 Set air damper Turn setting screw 1 until the scale shows the value determined A B 1 1 A Manual adjustment B Actuator optional ...

Page 30: ...ssure Determine the mixing pressure required for the preset combustion heat rating from the diagram and note down 16 22 20 18 24 26 28 30 32 34 36 38 40 42 2 7 2 6 2 5 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 1 Combustion heat rating kW 2 Mixing pressure mbar Guide values which may vary depending on combustion chamber resist ance ...

Page 31: ...boiler controller required Open fuel shut off devices Switch on voltage supply Illuminated push button lights up red Press illuminated push button for 1 second Burner starts in accordance with the programme sequence ch 3 3 4 2 Adjust combustion The pump pressure must be set according to the nozzle selected ch 4 2 Check pump pressure at pressure gauge Set pressure using pressure regulating screw 1 ...

Page 32: ...h leakage Remove oil measuring devices once commissioning is complete Check control and safety devices Check tightness of oil carrying components Enter combustion values and settings in the commissioning record and or test sheet Mount cover on burner Inform the operator about the use of the equipment Hand the installation and operating manual to the operator and inform him that this should be kept...

Page 33: ...ocument O2 content Check flue gas temperature Check flue gas temperature Ensure that the flue gas temperature complies with the data provided by the boiler manufacturer If necessary adjust flue gas temperature e g Increase burner capacity to avoid condensation in the flue gas ducts except on condensing units Reduce burner capacity to improve efficiency Adjust heat exchanger to the data provided by...

Page 34: ...Installation and operating instruction Oil burner WL5 1 B H 8 Shutdown 83272102 1 2019 03 La 34 76 8 Shutdown For breaks in operation Switch off burner Close fuel shut off devices ...

Page 35: ...s is listed in the service plan ch 9 2 Weishaupt recommends a service contract is entered into to ensure regular in spections The following components must only be replaced and must not be repaired combustion manager flame sensor actuator oil solenoid valve pressure switch Prior to every servicing Inform the operator about the extent of service work to be carried out Switch off mains switch of ins...

Page 36: ...me sensor Soiling Clean Damage 250 000 burner starts or 10 years 2 Replace Flame tube diffuser Soiling Clean Damage Replace Oil nozzle Soiling wear Replace Recommendation at least every 2 years Nozzle shut off Soundness Replace Oil pump filter Soiling Replace Oil hose Damage oil escaping Replace Recommendation every 5 years Oil solenoid valve Soundness 250 000 burner starts or 10 years 2 Replace o...

Page 37: ...5 1 B H 9 Servicing 83272102 1 2019 03 La 37 76 9 3 Service position Observe notes on servicing ch 9 1 Remove bolts 1 If necessary remove oil hoses Place the burner into the required service position Service position A and B A B 1 Service position C C 1 ...

Page 38: ...o not clean nozzles always fit new nozzles Place burner into service position B ch 9 3 Unplug ignition cable 4 Undo screw 1 and remove diffuser Counter hold on the nozzle body 3 using a spanner and remove nozzle 2 Fit new nozzle ensuring it is seated tightly Refit diffuser in reverse order Set nozzle distance ch 9 9 Set ignition electrodes ch 9 6 2 3 1 4 ...

Page 39: ...emove nozzle ch 9 4 Counter hold the nozzle assembly 4 using a spanner and remove nozzle holder 1 Remove valve piston 2 and compression spring 3 using a suitable tool e g pliers do not damage valve piston and O ring 1 2 3 4 Refitting Do not refit damaged valve pistons replace as necessary Refit nozzle shut off in reverse order Check nozzle distance ch 9 9 Set ignition electrodes ch 9 6 ...

Page 40: ... 6 Set ignition electrodes Observe notes on servicing ch 9 1 The ignition electrodes must not touch the nozzle s atomising cone Place burner into service position A ch 9 3 Check distance of ignition electrodes If necessary adjust ignition electrodes by slightly bending 1 0 2 0 mm 1 5 2 0 m m 2 0 2 5 mm ...

Page 41: ...102 1 2019 03 La 41 76 9 7 Removing the mixing head Observe notes on servicing ch 9 1 Unplug plug No 11 and 12 Unplug ignition cable 1 Remove flame sensor 5 Remove oil line 3 Remove pressure hose 6 from the mixing head Remove screws 2 Undo screws 4 Remove mixing head 1 4 2 5 3 6 ...

Page 42: ...La 42 76 9 8 Removing heat exchanger and temperature switch Observe notes on servicing ch 9 1 Remove mixing head ch 9 7 Remove nozzle ch 9 4 Remove screw 2 and remove nozzle assembly 1 Remove screw 3 and temperature switch 4 Remove heat exchanger 5 using a suitable tool e g pliers 2 3 5 4 5 1 ...

Page 43: ...Re tighten screw 1 A 2 5 3 mm 2 1 Check basic setting Dimension S1 can only be checked when the burner is mounted to a boiler door which is hinged open Hinge open boiler door or if necessary remove mixing head ch 9 7 Turn setting screw 1 until the indicating bolt 2 is flush with the nozzle as sembly cover dimension X 0 mm Check dimension S1 and or dimension Lx Set dimension S1 and or dimension Lx ...

Page 44: ...ervicing 83272102 1 2019 03 La 44 76 9 10 Removing the air regulator Observe notes on servicing ch 9 1 If necessary unplug actuator plug Place burner into service position A ch 9 3 Remove bolts 1 Remove intake housing 3 Remove bolts 4 Remove air regulator 2 2 3 4 1 ...

Page 45: ... Remove oil hoses 5 Remove oil line 4 Undo screws 2 and remove oil pump Refitting Install oil pump in reverse order and ensure correct alignment of coupling 3 ensure correct allocation of flow and return of the oil hoses CAUTION Damage to the oil pump caused by incorrect connection Mixing up supply and return can damage the oil pump Ensure correct connection of oil hoses to the supply and return o...

Page 46: ...efitting fan wheel Observe notes on servicing ch 9 1 Removing Place housing cover into service position C ch 9 3 Remove grub screw 1 and remove fan wheel Refitting Refit fan wheel in reverse order and ensure correct alignment on the motor shaft 2 screw in new grub screw 1 turn fan wheel to ensure it moves freely 2 1 1 2 ...

Page 47: ...n Oil burner WL5 1 B H 9 Servicing 83272102 1 2019 03 La 47 76 9 13 Remove burner motor Observe notes on servicing ch 9 1 Remove the oil pump ch 9 11 Remove fan wheel ch 9 12 Unplug plug 1 Hold motor and remove screws 2 Remove motor 3 1 2 ...

Page 48: ...2 1 2019 03 La 48 76 9 14 Removing and refitting oil pump filter Observe notes on servicing ch 9 1 Removing Close fuel shut off devices Remove bolts 1 Remove pump cover Replace filter 3 and gasket 2 2 3 1 Refitting Refit filter in reverse order ensuring sealing surfaces are clean ...

Page 49: ...WL5 1 B H 9 Servicing 83272102 1 2019 03 La 49 76 9 15 Replacing the fuse Observe notes on servicing ch 9 1 Remove all plugs from the combustion manager Remove screws from the combustion manager Remove combustion manager Replace fuse T6 3H IEC 127 2 5 ...

Page 50: ...ating External fuse has tripped 1 Check fuse Heating switch is set to Off Switch on heating switch Temperature limiter or pressure limiter on heat exchanger has triggered 1 Reset temperature limiter or pressure limiter on heat exchanger Low water safety interlock on heat ex changer has triggered 1 Top up water Reset low water safety interlock on heat exchanger Temperature regulator or pressure reg...

Page 51: ... read Press illuminated push button for 5 seconds Illuminated push button briefly lights up orange Illuminated push button flashes red Count between the flashing pauses and flashing signals and note down Rectify cause of fault see table Resetting WARNING Damage resulting from incorrect fault repair Incorrect fault repair can cause damage to the equipment and injure personnel Do not carry out more ...

Page 52: ...des Ignition cable defective Replace ignition cable Ignition unit defective Replace ignition unit Solenoid valve does not open Coil defective Replace coil Combustion manager does not detect a flame signal Flame sensor soiled Clean flame sensor Flame sensor defective Replace flame sensor Illumination insufficient Check burner setting Burner motor does not run Oil pump seized Replace oil pump ch 9 1...

Page 53: ...lashing 10 times Combustion manager fault Burner does not start Parameters have been changed Reset burner ch 10 1 2 Combustion manager de fective Reset burner ch 10 1 2 if fault reoccurs replace combustion manager 10 1 3 Illuminated push button flashes An irregularity is present The burner does not go to lockout Once the fault has been rectified the error code ceases Error codes without lockout Th...

Page 54: ...e worn Flame tube diffuser has heavy soot deposit Oil nozzle defective Replace nozzle Mixing head set incorrectly Set mixing head ch 9 9 Incorrect combustion air quantity Adjust burner Boiler room ventilated insufficient Ensure sufficient boiler room ventila tion Wrong oil nozzle Check nozzle type Nozzle distance incorrect Check nozzle distance adjust if necessary ch 9 9 Combustion pulsating or bu...

Page 55: ...n 83272102 1 2019 03 La 55 76 11 Technical documentation 11 1 Conversion table unit of pressure Bar Pascal Pa hPa kPa MPa 0 1 mbar 10 0 1 0 01 0 00001 1 mbar 100 1 0 1 0 0001 10 mbar 1 000 10 1 0 001 100 mbar 10 000 100 10 0 01 1 bar 100 000 1 000 100 0 1 10 bar 1 000 000 10 000 1 000 1 ...

Page 56: ...N 6 3A X3 3 C1 M1 M M20 X3 2 M max 16A F1 W FM 05 K1 K3 K2 5 4 6 3 2 12 11 13 X6 X3 F7 W FM 05 B15 Temperature or pressure regulator C1 Motor capacitor E1 Heat exchanger F1 External fuse F2 Temperature or pressure limiter F7 Internal unit fuse T6 3H IEC 127 2 5 M1 Burner motor M20 Air damper actuator optional P6 Control lamp lockout optional P11 Control lamp operation optional S1 Operating switch ...

Page 57: ...ical documentation 83272102 1 2019 03 La 57 76 K10 X3 6 K11 X3 5 h P11 1 X3 13 B1 X5 1 4 X3 4 T1 2 S3 K3 K2 B1 Flame sensor K10 Anti siphon valve optional K11 Solenoid valve P11 1 Hours counter optional S3 Remote reset optional T1 Ignition unit 2 Bus interface optional ...

Page 58: ...resistance or install oil supply pump or suction unit whilst observing the maximum supply pressure at the oil filter The suction resistance depends on suction line length and diameter pressure loss of oil filter and other components lowest oil level in the oil storage tank max 3 5 m below the oil pump If an oil feeder pump is installed max 1 5 bar supply pressure at oil filter max 0 7 bar supply p...

Page 59: ...upply and return can damage the oil pump Ensure correct connection of oil hoses to the supply and return of the pump If the oil is supplied via a single pipe system and automatic de aerator must be in stalled in front of the oil pump Two pipe system In a two pipe system the oil pump is vented automatically Ring main operation Weishaupt recommends the use of a ring main when operating several burne...

Page 60: ...perating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 60 76 13 Spares 1 03 1 01 1 02 1 20 1 14 1 16 1 13 1 19 1 07 1 18 1 08 1 17 1 17 1 09 1 10 1 19 1 12 1 18 1 11 1 12 1 11 1 05 1 06 1 15 1 04 1 07 ...

Page 61: ...d 241 050 01 247 WL5 on WTU S 241 050 01 267 1 09 Grommet for oil hose 241 050 01 177 1 10 Housing cover 241 050 01 037 1 11 Screw G1 8A DIN 908 409 004 1 12 Sealing ring 10 x 13 5 x 1 5 DIN 7603 441 033 1 13 Bracket for oil hose and cable Standard 241 400 01 367 WL5 on WTU S 241 050 01 327 1 14 Stay bolt cover Standard 241 050 01 357 WL5 on WTU S 241 050 01 347 1 15 Flame tube 241 050 14 042 1 16...

Page 62: ...Installation and operating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 62 76 2 02 2 07 2 03 2 05 2 01 2 08 2 09 2 06 2 04 ...

Page 63: ...r 4 0 µF 420V AC DB 713 473 2 03 Fan wheel TLR S 119 x 41 4 L S1 50Hz 241 050 08 012 2 04 Grub screw M6 x 8 w an cutter Tuflok 420 549 2 05 Air guide 241 050 01 207 2 06 Air regulator Standard with manual adjustment 241 050 02 042 with actuator 230 V 241 050 02 052 2 07 Intake duct 241 050 02 032 2 08 Manual adjustment 241 050 02 022 2 09 Actuator W St02 1 220 240V 50Hz 651 047 ...

Page 64: ...Installation and operating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 64 76 3 08 3 05 3 05 3 04 3 03 3 07 3 06 3 08 3 09 3 11 3 10 3 12 3 02 3 01 ...

Page 65: ...52 135 3 04 Oil line pump supply 241 050 06 028 3 05 Screwed union 24 SX LL04 ST 452 020 3 06 Pressure hose DN 4 286 mm for installation rotated by 180 491 246 3 07 Bypass plug BUZ 06 LL with nut 241 100 06 012 3 08 Oil hose DN 4 1200 mm Standard 491 126 diffusion resistant 491 131 3 09 Pressure hose DN 4 491 247 3 10 Sealing ring A10 x 14 x 4 0 DIN 7603 440 037 3 11 Sealing ring 10 x 14 x 1 5 DIN...

Page 66: ...rating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 66 76 4 25 4 01 4 03 4 26 4 02 4 24 4 27 4 25 4 05 4 18 4 21 4 18 4 20 4 04 4 10 4 15 4 12 4 14 4 07 4 10 4 09 4 06 4 08 4 11 4 13 4 23 4 22 4 16 4 17 ...

Page 67: ...097 4 12 U bolt 1096 for QRB1 1 600 566 AKG43 for QRB4 1 600 681 4 13 Flame sensor QRB1B 1 241 310 12 022 QRB4B 1 241 050 12 072 4 14 Plug 5 25 241 110 10 087 4 15 Indicating bolt M6 x 90 241 110 10 097 4 16 Adjusting lever bottom part 241 110 10 067 4 17 Adjusting lever top part 241 110 10 077 4 18 Screw M4 x 12 Torx Plus 20IP 409 237 4 19 Spring washer A6 DIN 137 431 615 4 20 Hexagonal nut M6 DI...

Page 68: ...rating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 68 76 4 25 4 01 4 03 4 26 4 02 4 24 4 27 4 25 4 05 4 18 4 21 4 18 4 20 4 04 4 10 4 15 4 12 4 14 4 07 4 10 4 09 4 06 4 08 4 11 4 13 4 23 4 22 4 16 4 17 ...

Page 69: ... 00 gph 45 SF Fluidics 602 062 0 40 gph 60 SF Fluidics 602 741 0 45 gph 60 SF Fluidics 602 742 0 50 gph 60 SF Fluidics 602 743 0 55 gph 60 SF Fluidics 602 744 0 60 gph 60 SF Fluidics 602 745 0 65 gph 60 SF Fluidics 602 746 0 75 gph 60 SF Fluidics 602 070 0 85 gph 60 SF Fluidics 602 071 1 00 gph 60 SF Fluidics 602 072 0 40 gph 60 HF Fluidics 602 725 0 45 gph 60 HF Fluidics 602 720 0 50 gph 60 HF Fl...

Page 70: ...rating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 70 76 4 25 4 01 4 03 4 26 4 02 4 24 4 27 4 25 4 05 4 18 4 21 4 18 4 20 4 04 4 10 4 15 4 12 4 14 4 07 4 10 4 09 4 06 4 08 4 11 4 13 4 23 4 22 4 16 4 17 ...

Page 71: ...nen 612 351 0 50 gph 60 HT Steinen 612 352 0 55 gph 60 HT Steinen 612 353 0 60 gph 45 S Steinen 612 002 0 65 gph 45 S Steinen 612 051 0 75 gph 45 S Steinen 612 004 0 85 gph 45 S Steinen 612 006 1 00 gph 45 S Steinen 612 008 0 60 gph 60 S Steinen 612 201 0 65 gph 60 S Steinen 612 250 0 75 gph 60 S Steinen 612 203 0 85 gph 60 S Steinen 612 206 1 00 gph 60 S Steinen 612 207 0 60 gph 60 H Steinen 612 ...

Page 72: ...Installation and operating instruction Oil burner WL5 1 B H 13 Spares 83272102 1 2019 03 La 72 76 5 05 5 06 5 06 5 04 5 02 5 07 5 08 5 01 5 03 ...

Page 73: ...30 V 50 60 Hz 600 470 Micro fuse T6 3H IEC 127 2 5 483 011 22 457 5 02 Cover clip AGK63 600 312 5 03 Bridging plug No 2 240 200 12 012 5 04 Plug unit ST18 7 716 549 5 05 Ignition unit type W ZG01V 230 V 100 VA 603 221 5 06 Screw M4 x 42 Combi Torx Plus 20IP 409 260 5 07 Plug cable No 3 motor 241 050 12 062 5 08 Plug cable No 5 solenoid valve 241 050 12 052 ...

Page 74: ...ling diagram 18 Ducted air intake 6 16 E Electrical connection 24 Electrical data 14 Electrodes 40 Emission 15 Emission class 15 Error code 51 Error codes 52 53 Errors 52 Excess air 33 Extraneous light 27 F Fabrication number 9 Fan motor 47 Fan pressure 27 30 Fan wheel 10 46 Fault 50 54 Fault history 51 Faults 53 Filter 48 58 Flame sensor 11 Flame signal 11 27 Flame tube 18 Flashing codes 52 53 Fl...

Page 75: ...sure regulating screw 31 Program sequence 12 Pulsating 54 Pump 10 22 27 45 59 Pump filter 48 Pump pressure 19 27 31 R Recommended nozzles 19 Refractory 18 Remote reset 24 Reset 51 Reset button 25 Return 22 Ring main operation 59 S Safety measures 6 Safety time 12 13 Sequence diagram 10 12 Serial number 9 Service 35 Service contract 35 Service interval 35 Service plan 36 Service position 37 Setting...

Page 76: ...Weishaupt GmbH 88475 Schwendi Weishaupt close by Addresses telephone numbers etc can be found at www weishaupt de We reserve the right to make changes All rights reserved Water heaters Energy storage The diverse program of potable water and energy storage for various heat sources includes storage volumes of 70 to 3 000 litres In order to minimize storage losses potable water cylinders from 140 to ...

Reviews: