Installation and operating instruction
Oil burner WL40Z-A
6 Operation
83298002 3/2019-11 La
35-112
6.2.4 Access level
In the access level, the configuration can be adapted relative to the burner type or
version.
In the parameter level, the display mode must be configured to
1
, to enable access
to parameters E0 … E4.
Press [G] and [L/A] simultaneously.
The access level is activated.
Press [+] key.
Parameter
E0
is displayed.
Press and hold [Enter] key and set the parameter using [+] or [–].
Press [+] to reach the next parameter.
Parameters Information
Setting range
E0
Burner type
0
: single fuel burner
1
: dual fue burner
E1
Operating mode
(display only, no adjust-
ment possible)
0
: intermittent operation
1
: continuous operation
E2
Flame sensor type
0
: ionisation electrode or flame sensor FLW
1
: switch input X3:14, flame sensor LFS1/RAR9
2
: flame sensor QRB4
E3
Fan configuration
0
: Off
1
: fan control
2
: fan control with fan monitoring
3
: VSD
4
: fan control according to modulating degree specified
5
: DAU control
6
…
255
: off
E4
Pre-ignition delay
0
…
4094
: the time (seconds) runs down from operating status
09
, then ig-
nition starts
OFF
: ignition only from operating status
15