Installation and operating instruction
Dual fuel burner WGL40/1-A ZM
6 Operation
83273402 1/2019-02 La
43-148
Flame sensor
A light emitting diode on the flame sensor indicates the current operating status.
LED off
Flame sensor not activated.
LED flashing
No flame.
LED continuously illuminated Flame present.
6.2.1 Info level
Burner data can be interrogated in the Info level .
Press [Enter] for approx. 0.5 seconds.
The Info level is activated.
Press [Enter] to reach the next information.
l,m³
No.
Information
0
– no function –
1
Hours run gas operation or oil operation stage 1
2
Hours run oil operation stage 2
3
Total burner starts
4
Device item number
5
Index of device item number
6
Device number
7
Production date (DDMMYY)
8
Fieldbus address
9
Valve proving behaviour
10
Oil pressure switch function
11
Not used
12
Not used
13
Analogue module EM3/3 or Fieldbus module EM3/2 available
0
: no
1
: yes
After information
13
or a waiting time of approx. 20 seconds the combustion man-
ager changes over to the operating level.