Installation and operating instruction
Gas burner WG30…/1-C ZM-LN
7 Commissioning
83299902 1/2019-02 La
48-124
7.1.6 Setting values
Set mixing head relative to the combustion heat rating required. For this, the dif-
fuser setting and the air damper setting should be matched.
Determine diffuser setting and air damper setting
Do not operate the burner outside of the capacity graph.
Determine the diffuser setting (dimension X) and air damper setting required
from the diagram and note down.
Example
Example 1
Example 2
Burner capacity required
165 kW
285 kW
Combustion chamber pressure
0.8 mbar
1.8 mbar
Diffuser setting (dimension X)
0 mm
8 mm
Air damper setting
37°
> 80°
-1,0
-1,5
-2,0
-0,5
0,0
0,5
1,0
1,5
2,0
325
400
375
350
300
275
200
175
150
125
100
75
50
25
0
2,5
3,0
3,5
250
225
5
10
15
0
10°
20°
30°
40° 50° 60°70°80°
5
6
1
2
4
3
1
Combustion heat rating [kW]
2
Combustion chamber pressure [mbar]
3
Air damper setting
4
Diffuser setting [mm] (dimension X)
5
Air damper setting range with diffuser setting closed (X = 0 mm)
6
Setting range dimension X with air damper setting > 80°