Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
7 Commissioning
83300002 1/2019-02 La
65-128
7.3.2 Set air pressure switch
The switch point must be checked and if necessary adjusted during commission-
ing.
Connect pressure measuring device for differential pressure measurement.
Start the burner.
Carry out differential pressure measurement across the whole capacity range of
the burner and determine the lowest differential pressure.
Calculate switch point (80 % of release pressure or lowest differential pressure).
Set the switch point determined at the setting cam
1
.
Example
Lowest differential pressure
7.5 mbar
Switch point air pressure switch (80 %) 7.5 mbar × 0.8 = 6.0 mbar
Site specific influences on the air pressure, (e g. by the flue gas system, heat ex-
changer, installation location or air supply) may make it necessary to vary the set-
ting of the air pressure switch.
1
7.4 Concluding work
Check control and safety devices.
Remove gas pressure measuring devices and close all test points.
Conclude valve proving of gas valve train (fourth test phase) [ch. 7.1.3].
Enter combustion values and settings in the commissioning record and/or test
sheet.
Enter setting values on the sticker
1
supplied.
Adhere sticker to the burner.
Mount cover on burner.
Inform the operator about the use of the equipment.
Hand the installation and operating manual to the operator and inform him that
this should be kept with the appliance.
Point out to operator that the installation should be serviced annually.
Brennereinstellung
Datum:
Stauscheiben-
einstellung:
mm
Gaseinstelldruck
bei Großlast:
mbar
Einstellungen am
Feuerungsmanager:
Voreinstellung Luftklappe
bei Großlast (P9):
°
Punkt G L/A n %
P0
P1
P2
P3
P4
P5
P6
P7
P8
P9
bo
bu
Unterschrift
1