Press [+] key.
Burner drives to operating point P
1
.
Press [ENTER].
Combustion manager changes to linearisation mode.
Confirm with [+] key.
Linearisation is initiated.
The display then shows operating point P
1
.
Calculation from P
1
to P
9
was carried out.
9. Optimising the operating points
Check combustion values
Press and hold [G] and optimise combustion values using [–] or [+] key.
Press [+] key.
Next operating point is initiated.
Repeat steps at each operating point until P9 has been reached.
Press [G] and [L/A] keys simultaneously.
The upper operating limit (
bo