Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
7 Commissioning
83300002 1/2019-02 La
46-128
7.1.5 Preset pressure regulator
Determine setting pressure
Add the combustion chamber pressure in mbar to the setting pressure into the gas
butterfly valve.
Determine setting pressure from the table and note down.
The details given for calorific value H
i
relate to 0 °C and 1013 mbar.
The table values have been calculated under ideal conditions. The values are there-
fore guide values for basic settings.
Full load
[kW]
Setting pressure
into gas butterfly
valve [mbar]
Min. connection pressure into isolating
valve [mbar]
(low pressure supply)
Nominal diameter valve train
¾"
1"
1½"
2"
DN 65 DN 80
W-MF
507
W-MF
512
W-MF
512
DMV
525
DMV
5065
DMV
5080
Natural Gas E: H
i
= 10.35 kWh/m
3
, d = 0.606
240
9.0
19
14
12
11
11
11
270
9.1
22
14
12
12
11
11
300
9.2
25
15
13
12
11
11
350
9.3
30
17
13
13
12
11
400
9.4
36
19
14
13
12
11
450
9.5
42
22
15
13
12
11
500
11.7
52
27
18
16
14
14
550
13.0
61
31
21
18
16
15
Natural Gas LL: H
i
= 8.83 kWh/m
3
, d = 0.641
240
11.3
26
17
15
14
13
13
270
11.2
29
18
15
14
13
13
300
10.9
33
19
15
14
13
13
350
10.7
40
22
16
15
13
13
360
10.7
41
22
16
14
13
13
400
11.7
49
26
18
16
14
14
450
13.0
60
30
21
18
16
15
500
14.3
72
35
23
20
17
17
550
16.8
86
42
27
23
20
19
Liquid Petroleum Gas: H
i
= 25.89 kWh/m
3
, d = 1.555
The selection is calculated for Propane, it can however, also be used
for Butane.
240
6.3
13
11
–
–
–
–
270
6.9
14
11
–
–
–
–
300
7.3
16
12
–
–
–
–
350
8.1
19
14
–
–
–
–
400
8.9
22
15
–
–
–
–
450
9.7
26
17
–
–
–
–
500
10.5
29
19
–
–
–
–
550
11.3
33
21
–
–
–
–