Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
6 Operation
83300002 1/2019-02 La
30-128
6 Operation
6.1 Operating panel
2
1
3
4
5
1
[G] Gas
Select gas butterfly valve actuator
2
[–]
Change values
3
[+]
4
[L/A] Air
Select air damper actuator
5
[Enter]
Reset burner:
call up information
press for approx. 0.5 seconds: Info level
press for approx. 2 seconds: Service level
3
and
5
[+] and [ENTER]
press simultaneously for approx. 2 seconds:
Parameter level (only possible with display
OFF
)
4
and
5
[L/A] and [Enter]
press simultaneously: select fan speed (only in
conjunction with variable speed drive)
Various actions are only triggered when the key is released, for example changing
the display, reset.
OFF function
Press [ENTER], [L/A] and [G] keys simultaneously.
Immediate lockout with error
18h
.
Operating level
The current actuator position and/or the fan speed can be displayed in the operat-
ing level (
10
).
Displaying gas butterfly valve setting:
Press key [G].
Displaying air damper setting:
Press key [L/A].
Displaying fan speed:
(only in conjunction with variable speed drive)
Press [Enter] and [L/A] simultaneously.
Flame signal
The flame signal can be displayed during commissioning (setting level) by using a
combination of keys.
Press [Enter], [L/A] and [G] keys simultaneously.
The flame signal is displayed.
Recommended flame signal, see Service level information
19