Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
3 Product description
83300002 1/2019-02 La
18-128
3.4 Technical data
3.4.1 Approval data
PIN (EU) 2016/426
CE-0085AS0311
PIN 2014/68/EU
Z-IS-TAF-MUC-14-05-376456-004
Basic standards
EN 676:2008
Additional standards, see EU conformity certifica-
tion.
3.4.2 Electrical data
Mains voltage / mains frequency
230 V/50 Hz
Consumption at start
max 856 W
Consumption during operation
max 756 W
Power consumption
max 3.8 A
Internal unit fuse
T6.3H, IEC 127-2/5
External fuse
max 16 AB
3.4.3 Ambient conditions
Temperature in operation
–15 … +40 °C
Temperature during transport / storage
–20 … +70 °C
relative humidity
max 80 %, no dew point
3.4.4 Fuels
Natural Gas E/LL
Liquid Petroleum Gas B/P
3.4.5 Emissions
Flue gas
To EN 676 the burner complies with emission class 3.
The NO
x
values are influenced by:
combustion chamber dimensions
flue gas system
combustion air (temperature and humidity)
medium temperature
Sound levels
Dual number noise emission values
Measured sound power level L
WA
(re 1 pW)
Uncertainty value K
WA
81
4
dB(A)
(1
dB(A)
Measured sound pressure level L
pA
(re 20 μPa)
Uncertainty value K
pA
77
4
dB(A)
(2
dB(A)
(1
Determined to ISO 9614-2.
(2
Determined at 1 metre distance from the front of the burner.
The measured noise levels plus uncertainty values form the upper limit value, which
could occur when measuring.