Installation and operating instruction
Gas burner WG10…/0-D ZM-LN
9 Servicing
83300902 1/2019-02 La
80-112
Determine the operating points from the sticker
1
.
Set the burner using these operating points and adjust [ch. 7.2].
Brennereinstellung
Datum:
Stauscheiben-
einstellung:
mm
Gaseinstelldruck
bei Großlast:
mbar
Einstellungen am
Feuerungsmanager:
Voreinstellung Luftklappe
bei Großlast (P9):
°
Punkt G L/A n %
P0
P1
P2
P3
P4
P5
P6
P7
P8
P9
bo
bu
Unterschrift
1
Deactivate E-Parameters
Following commissioning, set parameter
E
to
0
.
Press [Enter] and [+] keys simultaneously for approx. 2 seconds.
The parameter level is activated.
Press [+].
Press [Enter] key until parameter
E
is displayed.
Set parameter
E
to
0
.
E
-Parameters are not shown in the setting level.
Press [Enter] key twice.
The combustion manager returns to the operating level.